g
Digital Energy™ GT Series
3 - Operation
3.1Operation Panel
8 13 12 11 10
7
9
2
1
Fig. 3.1 Operating panel | 4 | 6 3 5 | |
1 Switch ‘I/TEST’ | - Switches on the UPS |
|
-In
-In ‘ON BATTERY’ mode it mutes the buzzer
2 Off switch | Switches off the UPS |
3LED ‘Bypass’ The UPS is in ‘BYPASS’ mode: the incoming utility power is channeled directly to the load. See also 3.3.5
4LED ‘Line’Indicates the condition of the utility input power. Continuously lighting up: the input power is OK,
Flashing : input voltage is too low, too high, or out of frequency,
Off: blackout or ultra high voltage (>150Vac)
5LED ‘On Line’ The UPS is operating in the (normal) ‘ON LINE’ mode
6LED ‘On Battery’ The UPS is operating in ‘ON BATTERY’
7Level bar- In ‘ON BATTERY’ mode: shows current battery capacity - In ‘ON LINE’ mode: showing current load level
8Battery LEDLevel bar shows current battery capacity
9Load LEDLevel bar shows current load level
10Battery low LED The battery is almost depleted
11Replace battery LED After abattery test the LED shows that the batteries are weak.
Battery replacement is recommended
12Overload LED The load exceeds the nominal UPS rating. After a short period of time the UPS will transfer to ‘BYPASS’ mode
13 Fault LED | The UPS is faulty |
OPM_GTU_TWR_1K0_3K0_XUS_V015 | 10 | DE GT Series: User manual rev date |