Digital Energy™ GT Series
4.2RS232
The
1- Monitoring charger status
2- Monitoring battery status and condition
3- Monitoring inverter status
4- Monitoring UPS status
5- Monitoring the AC utility power status
6- Turn on/off UPS on schedule for power saving
7- Adjust transfer voltage
Pin Assignment:
Pin 2 : PC receives line
Pin 3 : PC transmits line
Pin 5 : Signal ground.
Pin 4,6,7 : Reserved for plug and play function.
The UPS data is provided at 2400 bps baud rate and made up of 8
Hardware:
Baud rate | 2400 bps |
Data length | 8 bits |
Stop bit | 1 bit |
Parity | none |
Cabling:
Standard
4.3Dry Contact
Its major functions are some or all of the following:
1- to broadcast a warning when the AC utility power fails.
2- to save open files before the battery is exhausted.
3- to turn off the UPS via computer(s).
Pin Assignment:
Pin 1 : Normally open. When the battery voltage level is low, pin 1 and pin 5 are connected together via a photo coupler.
Pin 3 : UPS will shut down when a high level (5~12V) is applied for at least 3.8 seconds.
Pin 5 : Signal ground.
Pin 6,7 : Reserved.
Pin 8 : Normally open. When the AC utility fails, pin 8 and pin 5 are connected together via a photo coupler.
Cabling:
A special cable must be used with a pin assignment as follows:
PC (female) | UPS (male) |
Pin 1 | Pin 1 (Battery Low) |
Pin 3 | Pin 5 (GND) |
Pin 4 | Pin 3 (Shutdown) |
Pin 7 | Pin 6 |
Pin 7 | Pin 7 |
Pin 8 | Pin 8 (AC Fail) |