5

Table 5-3. Firmware Specifications

Tasks

256

 

 

States Per Task

255

 

 

Integer Variables (range ±32768 to +32767)

1000

 

 

Floating Point Variables (range +/± 1.175494E±38 to

1000

+/± 3.402823E+38) 32 BIT IEEE

 

Format.

 

 

 

String Variables

100

 

 

String Variable Size

80 Characters

 

 

Character Variables

64

 

 

PID Loops

20

 

 

Number of Timers

Unlimited

 

 

Timer Resolution

1/100second

 

 

Maximum Total Number of States

3000

 

 

Available Program Memory

46 K Bytes

 

 

Flags

1000

 

 

Total VariablesPlusI/O

3000

 

 

90-30 SLP I/O and Register Specifications

Type

Capacity

 

 

%I

512

 

 

%Q

512

 

 

%AI

128

 

 

%AQ

64

 

 

%T

256

 

 

%M

1024

 

 

%G

1280

 

 

%S

32

 

 

%SA

32

 

 

%SB

32

 

 

%SC

32

 

 

%R

2048

 

 

5-2

State Logic Processor for Series 90-30 PLC User's Guide ± March 1998

GFK-0726B

Page 27
Image 27
GE GFK-0726B manual SLP I/O and Register Specifications, Firmware Specifications