PMCS 6.15 Envelope definition

1) Physical System Size

75 power management devices (IEDs) (100 max),
150 I/O points (through IEDs or PLCs)
64 ethernet serial communications ports,
2 Modbus Monitors (maximum) using standard Modbus Monitor Proxy

2) HMI Application Size -

20,000 points/tags in HMI database (30K Max)
600 HMI alarms configured max
600 trended points (8 max per device)
HMI I/O rates, alarm rates, and logging rates not to exceed 750 pts/sec
13 HMI screens in CIMPLICITY utilizing Power Builder -10 device
type and 50 user screens
150 HMI screens in InTouch
5 DDE ports in CIMPLICITY with no more than 10 devices
configured per port
10% of tags connected to enterprise solution
Web-enabled only via CIMPLICITY WebView - no waveform or
event viewers
Maximum of one Viewer node

3) Special Application Issues

No redundancy
Components to be run as NT services by default

4) Performance

Response times:
1 second or less to open an HMI screen
1 seconds update time to populate a screen per device per serial
port*(Except for UR Device)
4 to 7 second time delay to display event in PMCS Event Viewer
1 second response time to make device change (settings/ command
coil) not including device feedback
1000 device events/ sec burst support
Configuration:
Maximum 15 devices per serial port
Device baud rates set to maximum
CIMPLICITY HMI points set for on-demand
Devices supporting 125 register block reads
Average CPU utilization <35%
99% system uptime
14 Getting Started CIMPLICITY PMCS Read-This-Book-First