Section 4 — Troubleshooting

Commercial-Industrial-Residential Portable Generator System

4.1 TROUBLESHOOTING

SYMPTOM

CAUSE

SOLUTION

Engine is running, but no AC

1.

Circuit breaker is open.

1.

Reset circuit breaker.

output is available.

2.

Poor connection or defective cord set.

2.

Check and repair.

 

3.

Connected device is bad.

3.

Connect another device that is in

 

 

 

 

good condition.

 

4.

Fault in generator.

4.

Contact Authorized Service Facility.

 

 

 

 

 

Engine runs good but bogs

1.

Short circuit in a connected load.

1.

Disconnect shorted electrical load.

down when loads are connected.

2.

Generator is overloaded.

2.

See “Don’t Overload the Generator” on page 9.

 

3.

Engine speed is too slow.

3.

Contact Authorized Service Facility.

 

4.

Shorted generator circuit.

4.

Contact Authorized Service Facility.

 

 

 

 

 

Engine will not crank.

 

10 amp fuse at rear of generator

 

Replace fuse with only an identical

 

 

control panel has melted open.

 

10-amp replacement fuse.

 

 

 

 

 

Engine will not start; or starts

1.

Dirty air cleaner.

1.

Clean or replace air cleaner.

and runs rough.

2.

Out of gasoline.

2.

Fill fuel tank.

 

3.

Stale gasoline.

3.

Drain fuel tank and fill with fresh fuel.

 

4.

Spark plug wire not connected to

4.

Connect wire to spark plug.

 

 

spark plug.

 

 

 

5.

Bad spark plug.

5.

Replace spark plug.

 

6.

Water in gasoline.

6.

Drain fuel tank; fill with fresh fuel.

 

7.

Overchoking.

7.

Put choke knob to No Choke position.

 

8.

Low oil level.

8.

Fill crankcase to proper level.

 

9.

Excessive rich fuel mixture.

9.

Contact Authorized Service Facility.

 

10. Intake valve stuck open or closed.

10. Contact Authorized Service Facility.

 

11. Engine has lost compression.

11. Contact Authorized Service Facility.

 

 

 

 

 

Engine shuts down during

1.

Out of gasoline.

1.

Fill fuel tank.

operation.

2.

Low oil level.

2.

Fill crankcase to proper level.

 

3.

Fault in engine.

3.

Contact Authorized Service Facility.

 

 

 

 

 

Engine lacks power.

1.

Load is too high.

1.

See “Don’t Overload the Generator” on page 9.

 

2.

Dirty air filter.

2.

Replace air filter.

 

3.

Engine needs to be serviced.

3.

Contact Authorized Service Facility.

Engine “hunts” or falters.

1.

Choke is opened too soon.

1.

Move choke to halfway position until

 

 

 

 

engine runs smoothly.

 

2.

Carburetor is running too rich or too

2.

Contact Authorized Service Facility.

 

 

lean.

 

 

 

 

 

 

 

No Battery Charge DC output.

1.

Battery posts are corroded.

1.

Clean battery posts.

 

2.

Battery cable is bad.

2.

Replace cable.

 

3.

Battery is defective.

3.

Check battery condition; replace if

 

 

 

 

defective.

 

4.

Receptacle is bad.

4.

Contact Authorized Service Facility.

 

 

 

 

 

 

 

 

 

19

Page 21
Image 21
Generac 004583-0 owner manual Troubleshooting

004583-0 specifications

Generac 004583-0 is a powerful and efficient home standby generator designed to provide reliable backup power during outages. This unit is specifically engineered to ensure that homeowners never have to worry about the disruption caused by power loss, keeping essential appliances and systems running smoothly, regardless of external conditions.

At the heart of the Generac 004583-0 is its robust engine, which delivers a peak output of 22 kW and is capable of running on either propane or natural gas. This fuel flexibility makes it an ideal choice for a variety of households, allowing users to select the fuel source that best fits their needs. The generator employs a high-performance, air-cooled engine featuring a durable construction that ensures long-lasting operation, and this reliability translates into peace of mind for homeowners.

One of the standout features of the Generac 004583-0 is its advanced Automatic Transfer Switch (ATS). The ATS seamlessly detects power outages and automatically switches the home’s electrical supply to the generator within seconds. This quick response is crucial for maintaining comfort and safety, especially during extreme weather conditions. The ATS also offers customizable settings, allowing homeowners to prioritize which circuits they want to power during an outage.

In addition to its seamless operation, the Generac 004583-0 integrates innovative technologies such as Mobile Link. This feature enables users to monitor the generator remotely via a smartphone app, providing real-time updates on the system’s status and maintenance needs. This connectivity enhances user experience and simplifies the management of the generator.

The generator is designed with a noise-reduction enclosure, ensuring that it operates quietly without disturbing daily life or neighborhood peace. Furthermore, the unit is built to withstand various weather conditions, featuring corrosion-resistant materials that ensure durability and a long service life.

Safety is paramount, and the Generac 004583-0 incorporates various safety features such as low oil and high-temperature shut-off sensors. These safeguards protect the engine and enhance the overall reliability of the device.

In summary, the Generac 004583-0 is a top-tier standby generator that combines power, efficiency, and advanced technology. With its robust engine, seamless automatic transfer capabilities, remote monitoring, and focus on safety and durability, it stands out as an excellent solution for homeowners seeking reliable backup power.