Generac 6294 Planning Your Installation, Typical Installation, Specifications, Model

Models: 6294

1 5
Download 5 pages 991 b
Page 2
Image 2
TABLE 1 - SPECIFICATIONS

TABLE 1 - SPECIFICATIONS

Model:

6294

# Circuits Provided on Transfer Switch

6

Max # Circuits

10

REQUIRED BREAKER FOR MAIN LOAD CENTER (not included)

60 amp 2-pole

Utility Main Breaker

60 amp 2-pole

Generator Main Breaker

30 amp 2-pole

Breakers Provided with Unit

2 – 15 amp 1-pole, 2 – 20 amp 1-pole, 1 – 20 amp 2-pole

Max GEN Watts

7500 continuous / 9000 surge

Max GEN Amps

30 Amps

Voltage

125/250 Volts

NEMA Type Enclosure

1 – Indoor Only

NEMA Configuration of Male Inlet in Power Inlet Box

L14-30

Phase

1

Minimum Gauge Cord Size

10/4

*Note: If Ground Fault Circuit Interrupters (GFCI), Arc Fault Circuit Interrupters (AFCI), or Surge Protector Circuit Breakers were used as the branch circuit protector in the main load center, they MUST be used in the transfer switch. GFCI and AFCI breakers require an isolated neutral connected from the load to the GFCI or AFCI. The load neutral needs to be connected with a wire nut to a 3-6 foot piece of white wire, run through the harness conduit to the transfer switch and connected to the "load neutral" lug or pigtail on the GFCI or ACFI breaker. Because GFCI and AFCI circuit breakers can take up more than one space, the overall maximum number of circuits may be reduced from the number shown. Not all brands of GFCI and Arc Fault breakers will fit.

STEP 1: PLANNING YOUR INSTALLATION:

1. Determine the appliances, circuits or equipment you want to operate with generator power during a power outage, such as:

Refrigerator/Freezer

Water Heater

Security System

Furnace Blower (gas/oil only)

Garage Door Opener

Sump Pump

TV / Radio

Microwave, Coffee Maker

Computer, Fax and Printer, Phone

Lighting

Well Pump

Aquarium

2.Determine the amps required for each appliance by reading the label on the appliance. IMPORTANT: No appliance should have an amperage rating that exceeds the GEN MAIN breaker rating in the transfer switch (See Table 1). The total amperage of all circuits can exceed the generator rating, but not all circuits will be able to be used concurrently.

3.Assign the circuit # in the load center to a circuit (A2, B2, etc.) in the transfer switch matching the size of the circuit breaker in the load center to the circuit breaker in the transfer switch. Once you’ve determined which circuits you want to connect and the appropriate amperage, you will be ready to begin installing your transfer switch.

4.The location of your load center/electrical panel in your home or business will determine where the transfer switch will be installed. Refer to the illustrations below. In addition to the transfer switch, you may need additional accessories to complete your generator transfer switch installation, such as a generator cord and power inlet box. Use the generator cord to connect your generator to the power inlet box outdoors. NEVER run a generator in an enclosed area! If your load center is in a basement or interior room, you should install a power inlet box on the exterior of your house or building to avoid running the generator cord through a door or window. Once you have all of the essential components for your specific needs, you may proceed with the installation.

5.Determine where you will install the power inlet box on an exterior wall at least 5 feet from any openings (doors, windows, vents, etc.). See Figure 1, below.

FIGURE 1: TYPICAL INSTALLATION:

Minimum

clearance from

any opening

2

Page 2
Image 2
Generac 6294 Planning Your Installation, Typical Installation, Specifications, Model, Minimum clearance from any opening