QT048
OPERATING DATA
|
|
|
| QT048 |
| |
KW RATING |
|
|
| 48 |
|
|
|
|
|
|
|
| |
ENGINE SIZE |
|
|
| 4.2 Liter |
| |
|
|
|
|
|
|
|
GENERATOR OUTPUT VOLTAGE/KW - 60Hz |
| kW - LP | Amps | kW - NG | Amps | CB Size |
120/240V, |
| 48 | 200 | 46 | 192 | 200 |
120/208V, |
| 48 | 166 | 46 | 160 | 175 |
120/240V, |
| 48 | 144 | 46 | 138 | 150 |
277/480V, |
| 48 | 72 | 46 | 69 | 80 |
|
|
|
|
|
|
|
GENERATOR LOCKED ROTOR KVA |
|
|
|
|
|
|
AVAILABLE @ VOLTAGE DIP OF 35% |
|
|
|
|
|
|
Single phase or 208 |
|
|
| 100 |
|
|
480V |
|
|
| 110 |
|
|
|
|
|
|
| ||
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) | Natural Gas |
| Propane |
| ||
|
| (ft3/hr.) | (gal/hr.) | cu ft/hr | ||
Exercise cycle |
| 88 |
| 0.94 |
| 34.4 |
25% of rated load |
| 205 |
| 2.23 |
| 81 |
50% of rated load |
| 370 |
| 4.03 |
| 147 |
75% of rated load |
| 516 |
| 5.62 |
| 204 |
100% of rated load |
| 661 |
| 7.20 |
| 261 |
|
|
|
|
|
|
|
ENGINE COOLING |
|
|
|
|
|
|
Air flow (inlet air including alternator and combustion air) | ft3/min. |
|
| 2,460 |
|
|
System coolant capacity | US gal. |
|
| 3.0 |
|
|
Heat rejection to coolant | BTU/hr. |
|
| 165,000 |
| |
Max. operating air temp. on radiator | °C (°F) |
|
| 60 (150) |
| |
Max. ambient temperature | °C (°F) |
|
| 50 (140) |
| |
|
|
|
|
|
|
|
COMBUSTION AIR REQUIREMENTS |
|
|
|
|
|
|
Flow at rated power 60 Hz | cfm |
|
| 235 |
|
|
|
|
|
|
|
|
|
SOUND EMISSIONS IN DBA |
|
|
|
|
|
|
Exercising at 7 meters |
|
|
| 60 |
|
|
Normal operation at 7 meters |
|
|
| 65 |
|
|
|
|
|
|
|
|
|
EXHAUST |
|
|
|
|
|
|
Exhaust flow at rated output 60 Hz | cfm |
|
| 395 |
|
|
Exhaust temp. at muffler outlet | °F |
|
| 1100 |
|
|
|
|
|
|
|
|
|
ENGINE PARAMETERS |
|
|
|
|
|
|
Rated synchronous RPM | 60 Hz |
|
| 1800 |
|
|
HP at rated KW | 60 Hz |
|
| 75 |
|
|
|
|
|
|
|
| |
POWER ADJUSTMENT FOR AMBIENT CONDITIONS |
|
|
|
|
| |
Temperature Deration |
|
|
|
|
|
|
3% for every 10 °C above - °C |
|
| 25 |
|
| |
1.65% for every 10 °F above - °F |
|
| 77 |
|
| |
Altitude Deration |
|
|
|
|
|
|
1% for every 100 m above - m |
|
| 183 |
|
| |
3% for every 1000 ft. above - ft. |
|
| 600 |
|
| |
|
|
|
|
|
|
|
RATING: All three phase units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with
KW rating is based on LPG Fuel and may derate with natural gas.