Generac QT04842KNAX manual Operating Data

Models: QT04842KNAX

1 4
Download 4 pages 25.39 Kb
Page 3
Image 3

QT048

OPERATING DATA

 

 

 

 

QT048

 

KW RATING

 

 

 

48

 

 

 

 

 

 

 

 

ENGINE SIZE

 

 

 

4.2 Liter

 

 

 

 

 

 

 

 

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

 

kW - LP

Amps

kW - NG

Amps

CB Size

120/240V, 1-phase, 1.0 pf

 

48

200

46

192

200

120/208V, 3-phase, 0.8 pf

 

48

166

46

160

175

120/240V, 3-phase, 0.8 pf

 

48

144

46

138

150

277/480V, 3-phase, 0.8 pf

 

48

72

46

69

80

 

 

 

 

 

 

 

GENERATOR LOCKED ROTOR KVA

 

 

 

 

 

 

AVAILABLE @ VOLTAGE DIP OF 35%

 

 

 

 

 

 

Single phase or 208 3-phase

 

 

 

100

 

 

480V 3-phase

 

 

 

110

 

 

 

 

 

 

 

ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)

Natural Gas

 

Propane

 

 

 

(ft3/hr.)

(gal/hr.)

cu ft/hr

Exercise cycle

 

88

 

0.94

 

34.4

25% of rated load

 

205

 

2.23

 

81

50% of rated load

 

370

 

4.03

 

147

75% of rated load

 

516

 

5.62

 

204

100% of rated load

 

661

 

7.20

 

261

 

 

 

 

 

 

 

ENGINE COOLING

 

 

 

 

 

 

Air flow (inlet air including alternator and combustion air)

ft3/min.

 

 

2,460

 

 

System coolant capacity

US gal.

 

 

3.0

 

 

Heat rejection to coolant

BTU/hr.

 

 

165,000

 

Max. operating air temp. on radiator

°C (°F)

 

 

60 (150)

 

Max. ambient temperature

°C (°F)

 

 

50 (140)

 

 

 

 

 

 

 

 

COMBUSTION AIR REQUIREMENTS

 

 

 

 

 

 

Flow at rated power 60 Hz

cfm

 

 

235

 

 

 

 

 

 

 

 

 

SOUND EMISSIONS IN DBA

 

 

 

 

 

 

Exercising at 7 meters

 

 

 

60

 

 

Normal operation at 7 meters

 

 

 

65

 

 

 

 

 

 

 

 

 

EXHAUST

 

 

 

 

 

 

Exhaust flow at rated output 60 Hz

cfm

 

 

395

 

 

Exhaust temp. at muffler outlet

°F

 

 

1100

 

 

 

 

 

 

 

 

 

ENGINE PARAMETERS

 

 

 

 

 

 

Rated synchronous RPM

60 Hz

 

 

1800

 

 

HP at rated KW

60 Hz

 

 

75

 

 

 

 

 

 

 

 

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

 

 

 

 

 

Temperature Deration

 

 

 

 

 

 

3% for every 10 °C above - °C

 

 

25

 

 

1.65% for every 10 °F above - °F

 

 

77

 

 

Altitude Deration

 

 

 

 

 

 

1% for every 100 m above - m

 

 

183

 

 

3% for every 1000 ft. above - ft.

 

 

600

 

 

 

 

 

 

 

 

 

RATING: All three phase units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1, BS5514, and DIN6271. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition. Design and specifications are subject to change without notice.

KW rating is based on LPG Fuel and may derate with natural gas.

Page 3
Image 3
Generac QT04842KNAX manual Operating Data