QT048
OPERATING DATA
  | 
  | 
  | 
  | QT048  | 
  | |
KW RATING | 
  | 
  | 
  | 48  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
ENGINE SIZE | 
  | 
  | 
  | 4.2 Liter  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
GENERATOR OUTPUT VOLTAGE/KW - 60Hz | 
  | kW - LP | Amps | kW - NG | Amps  | CB Size | 
120/240V,   | 
  | 48  | 200  | 46  | 192  | 200  | 
120/208V,   | 
  | 48  | 166  | 46  | 160  | 175  | 
120/240V,   | 
  | 48  | 144  | 46  | 138  | 150  | 
277/480V,   | 
  | 48  | 72  | 46  | 69  | 80  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
GENERATOR LOCKED ROTOR KVA | 
  | 
  | 
  | 
  | 
  | 
  | 
AVAILABLE @ VOLTAGE DIP OF 35% | 
  | 
  | 
  | 
  | 
  | 
  | 
Single phase or 208   | 
  | 
  | 
  | 100  | 
  | 
  | 
480V   | 
  | 
  | 
  | 110  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | ||
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) | Natural Gas  | 
  | Propane  | 
  | ||
  | 
  | (ft3/hr.)  | (gal/hr.)  | cu ft/hr  | ||
Exercise cycle  | 
  | 88  | 
  | 0.94  | 
  | 34.4  | 
25% of rated load  | 
  | 205  | 
  | 2.23  | 
  | 81  | 
50% of rated load  | 
  | 370  | 
  | 4.03  | 
  | 147  | 
75% of rated load  | 
  | 516  | 
  | 5.62  | 
  | 204  | 
100% of rated load  | 
  | 661  | 
  | 7.20  | 
  | 261  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
ENGINE COOLING | 
  | 
  | 
  | 
  | 
  | 
  | 
Air flow (inlet air including alternator and combustion air)  | ft3/min.  | 
  | 
  | 2,460  | 
  | 
  | 
System coolant capacity  | US gal.  | 
  | 
  | 3.0  | 
  | 
  | 
Heat rejection to coolant  | BTU/hr.  | 
  | 
  | 165,000  | 
  | |
Max. operating air temp. on radiator  | °C (°F)  | 
  | 
  | 60 (150)  | 
  | |
Max. ambient temperature  | °C (°F)  | 
  | 
  | 50 (140)  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
COMBUSTION AIR REQUIREMENTS  | 
  | 
  | 
  | 
  | 
  | 
  | 
Flow at rated power 60 Hz  | cfm  | 
  | 
  | 235  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
SOUND EMISSIONS IN DBA  | 
  | 
  | 
  | 
  | 
  | 
  | 
Exercising at 7 meters  | 
  | 
  | 
  | 60  | 
  | 
  | 
Normal operation at 7 meters  | 
  | 
  | 
  | 65  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
EXHAUST  | 
  | 
  | 
  | 
  | 
  | 
  | 
Exhaust flow at rated output 60 Hz  | cfm  | 
  | 
  | 395  | 
  | 
  | 
Exhaust temp. at muffler outlet  | °F  | 
  | 
  | 1100  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
ENGINE PARAMETERS  | 
  | 
  | 
  | 
  | 
  | 
  | 
Rated synchronous RPM  | 60 Hz  | 
  | 
  | 1800  | 
  | 
  | 
HP at rated KW  | 60 Hz  | 
  | 
  | 75  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
POWER ADJUSTMENT FOR AMBIENT CONDITIONS | 
  | 
  | 
  | 
  | 
  | |
Temperature Deration  | 
  | 
  | 
  | 
  | 
  | 
  | 
3% for every 10 °C above - °C  | 
  | 
  | 25  | 
  | 
  | |
1.65% for every 10 °F above - °F  | 
  | 
  | 77  | 
  | 
  | |
Altitude Deration  | 
  | 
  | 
  | 
  | 
  | 
  | 
1% for every 100 m above - m  | 
  | 
  | 183  | 
  | 
  | |
3% for every 1000 ft. above - ft. | 
  | 
  | 600  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
RATING: All three phase units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with 
KW rating is based on LPG Fuel and may derate with natural gas.