TO SET HOUR CLOCK

Touch SET HOUR CLOCK to see setting. To change, touch and hold until hour closest to the actual time appears in the display. MAKE SURE A.M. AND P.M. ARE SET PROPERLY. (Minutes will NOT show on display.)

TO SET THE TIMER

NOTE: SET HOUR CLOCK before attempting to set timer functions.

The TIMER ON/OFF times can be set a minimum of one hour apart and a maximum of twenty-three hours apart.

STOP TIME - Touch A/C STOP and hold until the hour the unit needs to shut off appears in the display A.M. or P.M.)

START TIME - Touch A/C START and hold until the hour the unit needs to come on appears in the display (A.M. or P.M.)

Touch TIMER ON (light on) to activate the timer function. Touch TIMER OFF (light off) to cancel the timer function desired. Once the on and off times have been selected, they will remain in memory, and cycle daily until changed, or until the unit is subject to a power interruption.

TESTING THE ELECTRONIC CONTROL

2003 XQ BOARDS & QME BOARDS Checking Room Temperature:

1.Check the room temperature at the electronic control pad by pressing the "FAN SPEED" button and the temperature "UP" button at the same time on XQ models.

2.Check the room temperature at the electronic control pad by pressing at the same time the "FAN SPEED" button and the "WARMER" button on QME models.

The indoor temperature will display for 10 seconds. Indoor temperature can be viewed in all modes, including the TEST mode. The display can be changed back to SET temperature by pressing any key, except the ON/OFF button, or after 10 seconds has elapsed.

Activating Test Mode: Activate test mode by pressing at the same time the "MODE" button and the temperature "DOWN" button on XQ models. LEDs for Hour, Start, and Stop will blink 1 bps while Test Mode is active.

Activate test mode by pressing at the same time the "MONEY SAVER" button and the "FILTER ALERT" button on QME models. LED for the Filter Alert will blink 1 bps while Test Mode is active.

Test Mode has duration of 90 minutes. Test Mode can be activated under any conditions, including Off. Test Mode is cancelled by pressing the On/Off button, unplugging the unit, or when the 90 minutes is timed out. All settings revert to the factory default settings of Cool, 75 degrees F, Timer and Set Hour features are nonfunctional.

Test Mode overrides the three-minute lockout, all delays for compressor and fan motor start / speed change, and no delay when switching modes.

Test Mode default settings are ON, Money Saver, 60 degrees F, and High fan speed.

Activating Error Code Mode: (Submode of Test Mode) Unit has to be in Test Mode to enter Error Code Mode

1.Activate Error Code Mode by pressing the "TIMER ON/ OFF" button on XQ models. LED for the "TIMER ON/OFF" will flash 1 bps while Error Code Mode is active. Pressing the "TEMP/HR + " button will display 00. Consecutive presses will scroll through all error codes logged. Press the "TEMP/HR - " button to see the reverse order of all error codes logged. When the end of logged error codes is reached the temperature set point will appear.

Activate Error Code Mode by pressing at the same time the "A/C START" button and the "ON/OFF" button on QME models. LED for the "TIMER ON/OFF" will flash 1 bps while Error Code Mode is active. Pressing the "WARMER" button will display 00. Consecutive presses will scroll through all error codes logged. Press the "COOLER" button to see the reverse order of all error codes logged. When the end of logged error codes is reached the temperature set point will appear.

IMPORTANT: Error Codes are cleared from the log by exiting from Error Code Mode. To exit on XQ mod- els, press Timer On/Off button. To exit QME models, press A/C Start and On/Off buttons. Or unplug unit to exit Error Code Mode. Plug unit in after 5 seconds to resume normal operation of unit.

TESTING THE ELECTRONIC CONTROL

ERROR CODE LISTINGS

E1 SHORT CYCLE SITUATION: Defined as (compressor powered on before the three minute time delay ten times in one hour. Investigate and correct short cycling problem.

E2 KEYBOARD STUCK ERROR: If key button(s) are pressed continuously for twenty seconds or more. If MODE key is stuck, unit will default to cool. Exit Error Code Mode to see if error "E2" is no longer displayed and unit is functioning. Replace board if "E2" still displays after exiting Error Code Mode.

E3 FROST PROBE OPEN: Normal operation is allowed. Ohm frost probe. Replace probe if ohm value not read. If ohm value present replace board.

E4 FROST PROBE SHORT: Normal operation allowed. Replace probe.

E5 INDOOR PROBE OPEN: Control assumes indoor ambient temperature is 90 degree F and unit will operate. Ohm indoor probe. Replace probe if ohm value not read.

E6 INDOOR PROBE SHORT: Control assumes ambient temperature is 90 degree F and unit will operate. Replace probe.

NOTE: All Error Code displays for Frost & Indoor Probe will allow unit to operate. Unit may or will ice up if faulty components not replaced.

FROST PROBE SENSOR: disables compressor at 35 degrees F.

INDOOR PROBE SENSOR: Control range is 60 degrees F to 90 degrees F +/- 2 degrees F.

Indoor temperature will be displayed by pressing:

23

Page 23
Image 23
Friedrich racservmn service manual To SET Hour Clock, To SET the Timer, Testing the Electronic Control

racservmn specifications

Friedrich Racervmn is an innovative name in the realm of precision engineering, making significant strides in the development of advanced technologies for various industries. This company stands out due to its commitment to creating high-quality, reliable, and efficient products that cater to the diverse needs of its clientele.

One of the main features of Friedrich Racervmn is its focus on research and development. The company invests heavily in R&D to push the boundaries of what is technically possible. This dedication results in the continuous improvement of their product line and the introduction of cutting-edge solutions that leverage the latest advancements in technology.

Among the distinctive technologies used by Friedrich Racervmn is their proprietary manufacturing process, which integrates automation and robotics to enhance efficiency and precision. This not only speeds up production times but also ensures that the products maintain a consistently high quality. The use of Computer Numerical Control (CNC) machines in their processes allows for intricate designs and complex geometries that meet rigorous industry standards.

Moreover, Friedrich Racervmn utilizes innovative materials in their products to ensure durability and performance under various conditions. These materials are selected based on their specific properties, such as strength, weight, and resistance to environmental factors, ensuring that the final output exceeds customer expectations.

Another hallmark of Friedrich Racervmn is their commitment to sustainability. The company actively seeks ways to minimize its environmental footprint by optimizing resource use and incorporating eco-friendly practices throughout its manufacturing processes. This is reflected in their efforts to design products that are not only high-performing but also energy-efficient, helping customers reduce their carbon emissions.

Friedrich Racervmn’s customer service stands out as well. Their team is dedicated to providing exceptional support, ensuring that clients receive personalized attention and solutions tailored to their unique needs. This customer-centric approach is a fundamental part of their philosophy and has contributed to building strong and lasting relationships within the industry.

In summary, Friedrich Racervmn is a leader in precision engineering, recognized for its advanced technologies, innovative manufacturing processes, commitment to sustainability, and outstanding customer service. The company’s focus on quality and innovation positions it as a vital player in the modern industrial landscape, continuously pushing the envelope toward a more technologically advanced and environmentally conscious future.