Section 2 – Operation

2.6 STOPPING THE GENERATOR

1.Turn OFF all electrical loads using the means provided (such as a main circuit breaker or transfer switch).

2.Let generator run at no-load for a few minutes, to stabilize internal engine generator temperatures.

3.Place the Start/Stop switch in its STOP position.

2.7 APPLYING LOADS TO GENERATOR

Recreational Vehicle Generator

Induction type motors (such as those that run the vehicle’s furnace fan, refrigerator, air conditioner, etc.) need about 2-1/2 time more watts of power for starting than for running (for a few seconds dur- ing motor starting). Be sure to allow for this when connecting electrical loads to the generator. First, figure the watts needed to start electric motors in the system. To that figure, add the running watt- ages of other items that will be operated by the generator.

When applying electrical loads to the generator,

• Do not apply heavy electrical loads for the first two

observe these guidelines:

or three hours of operation.

Before applying electrical loads, let the generator stabilize and warm up for a minute or two.

DO NOT overload the generator.

‹2.7.1 LETTING THE ENGINE STABILIZE

The generator supplies correct rated voltage only at the proper governed speed. Some electrical appli- ances may be extremely sensitive to voltage. Incorrect voltages can damage such appliances.

If electrical loads are applied at reduced operating speeds, such loads imposed on the engine when suf- ficient power is not available may shorten engine life. Never turn ON electrical loads until after the generator engine has started and stabilized at no-load.

2.8 DO NOT OVERLOAD THE GENERATOR

2.9 PROTECTION SYSTEMS

‹2.9.1 LOW OIL PRESSURE SWITCH

This switch (Figure 2.2) has normally closed (N.C.) contacts that are held open by engine oil pressure dur- ing cranking and operating. Should oil pressure drop below a preset level, switch contacts close, and the engine automatically shuts down. The unit should not be restarted until oil is added.

‹2.9.2 HIGH TEMPERATURE SWITCH

This switch (Figure 2.2), which has normally open (N.O.) contacts, is mounted near the oil filter. The contacts close if the temperature should exceed approximately 305º F (152º C), initiating an engine shutdown.

Read the rated wattage/amperage capacity of the generator on the generator data label (see "Generator Identification").

Figure 2.2 – Low Oil Pressure and

High Temperature Switches

High Temperature Switch

Applying electrical loads in excess of the unit’s rated capacity will cause the engine/generator to automati- cally shut down.

To avoid overloading, add up the wattage of all con- nected electrical lighting, appliance, tool and motor loads. This total should not be greater than the generator’s rated wattage capacity.

Most lighting, appliance, tool and motor loads indicate their required watts on their nameplate or data plate. For light bulbs, simply note the wattage rating of the bulb.

If a load does not show its rated wattage, multiply that load’s rated VOLTS times AMPS to obtain

WATTS.

Low Oil Pressure Switch

9

Page 11
Image 11
Generac Power Systems 004709-0 owner manual Stopping the Generator, Applying Loads to Generator

004709-0 specifications

Generac Power Systems has established itself as a leader in the home backup generator market with its innovative products, and the Generac 004709-0 is no exception. Designed for homeowners seeking reliable power solutions during outages, this generator ensures peace of mind and uninterrupted operation for essential appliances and electronics.

One of the primary features of the Generac 004709-0 is its robust power output. With a powerful 7,500 running watts and a surge capacity of 9,000 watts, it can efficiently handle large loads, including central air conditioning units, refrigerators, and heat pumps. This generator operates on gasoline, providing an accessible fuel source readily available at most retail locations.

Equipped with a durable 420cc engine, the 004709-0 combines efficiency with exceptional performance. It features a low-oil shutdown system, which safeguards the engine from damage by automatically shutting off when oil levels become critically low. This feature ensures longevity and reliability, making it a dependable choice for homeowners.

The portability of the Generac 004709-0 is another notable characteristic. Weighing approximately 130 pounds, it comes with a built-in handle and sturdy wheels for easy transportation. This feature allows users to move the generator effortlessly from storage to the desired location, which is especially convenient during an emergency.

In addition to power and portability, the Generac 004709-0 boasts user-friendly controls. The control panel includes four 120V household outlets, a 12V automotive outlet, and a circuit breaker, offering flexibility for various connections. Furthermore, the generator is equipped with an easy-to-read fuel gauge and a low-fuel warning light, enhancing operational visibility.

Safety is also paramount in the design of this generator. It includes a powerful muffler that significantly reduces noise and meets stringent regulations for operation in residential areas. Additionally, the 004709-0 incorporates advanced technologies like the PowerDial which allows users to select the correct power level needed for various tasks easily.

Overall, the Generac Power Systems 004709-0 stands out due to its powerful output, user-friendly design, and safety features. Homeowners can rely on this generator to keep their homes powered during outages, ensuring comfort and security for themselves and their families. With its combination of innovation and practicality, the 004709-0 continues to exemplify Generac's commitment to quality and excellence in power solutions.