Generac Power Systems 005220-0 Repair Parts, ‹Battery Maintenance, ‹Battery Replacement, Danger

Models: 005220-0

1 60
Download 60 pages 25.78 Kb
Page 19
Image 19
‹BATTERY MAINTENANCE

Standby Generator Sets

Maintenance

‹BATTERY MAINTENANCE

The battery should be inspected per the “Service Schedule” section. The following procedure should be followed for inspection:

1.Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.

2.Check the battery fluid level of unsealed batteries and, if necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP WATER IN BATTER- IES.

3.Have the state of charge and condition checked. This should be done with an automotive-type bat- tery hydrometer.

‹BATTERY REPLACEMENTREPAIR PARTS DANGER

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charg- ing. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shat- ter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smok- ing, open flame, sparks or any spark producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely caus- tic sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If the fluid is spilled, flush the affected area immediately with clear water.

Do not use any jumper cables or booster battery to crank and start the generator engine. If the battery has completely discharged, remove it from the generator for recharging.

Be sure the AUTO/OFF/MANUAL switch is set to the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.

Be sure the 120VAC power supply to the battery is turned OFF, or sparking may occur at the bat- tery posts as the cables are attached and cause an explosion.

‹BATTERY REPLACEMENT

When replacing batteries, use the same number and the type of battery that follows:

 

BCI Group No.

CCA

 

 

24F-6

525 @ 0 deg. F

 

 

 

 

 

NOTE:

The BCI number should be located directly on the battery.

REPAIR PARTS

The latter portion of this manual consists of exploded views, parts lists and electrical data pertaining to this generator set. The parts lists consist of (a) an item number, (b) a part number, (c) the quantity required, and (d) a description of the part. The item number corresponds to an identical number on the exploded view drawing.

 

Periodic Replacement Parts

Part Name

Part Number

Oil Filter

# 0E7415

Radiator Cap

# 046627

Air Cleaner

# 0A4637

Spark Plug

Champion # RC12LC4

08/05

0 .Rev Maint001

10-4

Page 19
Image 19
Generac Power Systems 005220-0 owner manual Repair Parts, ‹Battery Maintenance, ‹Battery Replacement, Danger