Generac Power Systems 005220-0 owner manual Installation, Preparation Before START-UP

Models: 005220-0

1 60
Download 60 pages 25.78 Kb
Page 13
Image 13

Standby Generator Sets

Installation

INSTALLATION

‹PRIOR TO INITIAL START-UP

Refer to the separate “Installation Guide QT Product Line” supplied with the unit.

PREPARATION BEFORE START-UP

The instructions in this section assume that the standby generator has been properly installed, ser- viced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules”, as well as all other safety information in this manual, before attempting to operate this (and related) equipment.

Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service intervals, please refer to the “Maintenance” section and the “Service Schedule”.

‹TRANSFER SWITCH

If this generator is used to supply power to any elec- trical system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed. The transfer switch prevents elec- trical backfeed between two different electrical sys- tems. (For additional information, see the applicable transfer switch manual for this unit.) The transfer switch, as well as the generator and other standby components, must be properly located and mounted in strict compliance with applicable codes, standards and regulations.

‹FUEL SYSTEM

Make sure the fuel supply system to the genera- tor (a) delivers the correct fuel at the correct pres- sure and (b) is properly purged and leak tested according to code. No fuel leakage is permitted. See “Specifications” for more information.

‹GENERATOR SET LUBRICATION

Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See “Specifications” and “Engine Oil Recommendations”.

NOTE:

This engine is shipped from the manufacturer with “break-in” oil. This oil should be changed after 30 hours of operation.

Check the oil level in the generator gearbox (if so equipped) prior to initial use and at the intervals indicated by the “Service Schedule.” The recom- mended oil is SAE 90 gear lubricant.

Also, if the engine is equipped with a mechanical gov- ernor, make sure the governor is properly lubricated with clean engine oil.

8-1

Prior to initially starting the generator, it must be properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quantities of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure.

‹ENGINE COOLANT

Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See “Specifications” and “Coolant” sections.

‹BELT TENSION

Check-the engine-fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approximately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8- inch (10 to 16 mm).

‹ELECTRICAL SYSTEM

Make sure the generator is properly connected to an approved earth ground.

Make sure the generator battery is fully charged, properly installed and interconnected, and ready for use.

Check to ensure that there are no loose electrical con- nections. Restrain any loose wires to keep them clear of any moving generator set components.

INITIAL INSPECTION FOR QT GENSET STARTUP

Inspect for the following.

Freight Damage.

Manuals present.

Fluid Levels ( Oil, coolant, battery, Gear Drive).

Correct fuel piping.

Correct muffler installation for QT50, QT70, QT100 - QT150.

Adequate air flow, clearances and ventilation per installation drawings and applicable codes.

Correct AC and DC wire size, connections and grounding. Control and communication wiring to/ from the transfer switch must be run in a separate conduit from the AC power leads.

Battery charger connection to 120 VAC.

Communication wires connected between transfer switch and generator (HTS only).

Unit secured to pad.

11/05 A .Rev Install001

Page 13
Image 13
Generac Power Systems 005220-0 Installation, Preparation Before START-UP, Initial Inspection for QT Genset Startup

005220-0 specifications

Generac Power Systems has made a name for itself in the world of backup and portable power solutions, and the Generac 005220-0 is no exception. This advanced generator is engineered for reliability and efficiency, making it an ideal choice for home and business owners who require a dependable source of power during outages.

One of the standout features of the Generac 005220-0 is its powerful Generac OHV engine, designed for optimal performance and longevity. This four-stroke engine provides ample power, ensuring that essential appliances and systems can continue to operate without interruption during power failures. With a 7,500 running watt and 9,375 starting watt capacity, it can handle a significant load, making it suitable for various applications, from powering essential home appliances to running tools on job sites.

Additionally, the 005220-0 is equipped with a large, durable 9.5-gallon fuel tank, allowing for extended run times. Depending on the load, users can expect several hours of operation without needing to refuel, which is a critical consideration for emergencies. The economical fuel consumption is a plus, providing significant runtime while minimizing costs.

In terms of technology, the Generac 005220-0 utilizes a variety of features that enhance its functionality and ease of use. The integrated Control Panel includes multiple outlets, enabling users to connect multiple devices simultaneously. Further, it comes with a digital hour meter, which helps track maintenance intervals and runtime, ensuring that the generator remains in optimal working condition.

Safety is a priority with the 005220-0, as it incorporates low-oil shutdown technology, which automatically turns off the engine when oil levels are dangerously low. This feature prevents potential engine damage, extending the lifespan of the generator. Additionally, it is equipped with a circuit breaker, protecting against overloads, thereby safeguarding both the generator and connected devices.

One of the key characteristics of the Generac 005220-0 is its portability. The generator is designed with a sturdy frame and comes with never-flat wheels and a folding handle, making it easy to transport to various locations as needed.

In summary, the Generac 005220-0 stands out for its powerful performance, extended runtime, user-friendly features, and safety attributes. Whether for home backup or job site power, it provides confidence and reliability, ensuring that power needs are met even in challenging circumstances.