Standby Generator Sets

Service Schedule

SERVICE SCHEDULE

30 KW - 150 KW STANDBY GAS ENGINE DRIVEN GENERATOR SETS

The following is a recommended maintenance schedule for standby gas engine driven generator sets from 30kW to 150 kW in size. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application. They will need to be decreased (performed more frequently) if the unit is used in a severe application. Use calendar time, from the previous maintenance interval to determine the next required maintenance interval.

Service Maintenance Interval Information:

The various service maintenance intervals are designated by interval numbers as follows:

1An early inspection of the generator set to insure it is ready to operate when required and to identify any poten- tial problem areas.

This inspection may be performed by the end user providing the following safety steps are taken to prevent the engine from starting automatically without warning:

To prevent injury, perform the following steps in the order indicated before starting any maintenance:

Disable the generator set from starting and/or connecting to the load by setting the control panel Auto/Off/ Manual switch to the “OFF” position.

Remove the 15 amp control panel fuse.

Turn off the battery charger.

Remove the negative battery cable.

The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condition

from burning out sensitive control panel components and circuits.

Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal operation when required.

2A wear-in service inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.

Performed ONLY ONCE following the first three months or the first 30 hours of operation after purchase of the unit.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

3An operational inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.

Performed semi-annually or following each 50 hours of operation of the unit.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

4A mid-level inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.

Performed annually or following each 100 hours of operation of the unit.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

5A comprehensive inspection of the generator set to insure it is properly serviced and ready to operate and carry the load when required, and to identify any potential problem areas.

Performed annually or following each 250 hours of operation of the unit.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

11-1

09/05 A .Rev SrvSchd001

Page 20
Image 20
Generac Power Systems 005220-0 owner manual Service Schedule, KW 150 KW Standby GAS Engine Driven Generator Sets

005220-0 specifications

Generac Power Systems has made a name for itself in the world of backup and portable power solutions, and the Generac 005220-0 is no exception. This advanced generator is engineered for reliability and efficiency, making it an ideal choice for home and business owners who require a dependable source of power during outages.

One of the standout features of the Generac 005220-0 is its powerful Generac OHV engine, designed for optimal performance and longevity. This four-stroke engine provides ample power, ensuring that essential appliances and systems can continue to operate without interruption during power failures. With a 7,500 running watt and 9,375 starting watt capacity, it can handle a significant load, making it suitable for various applications, from powering essential home appliances to running tools on job sites.

Additionally, the 005220-0 is equipped with a large, durable 9.5-gallon fuel tank, allowing for extended run times. Depending on the load, users can expect several hours of operation without needing to refuel, which is a critical consideration for emergencies. The economical fuel consumption is a plus, providing significant runtime while minimizing costs.

In terms of technology, the Generac 005220-0 utilizes a variety of features that enhance its functionality and ease of use. The integrated Control Panel includes multiple outlets, enabling users to connect multiple devices simultaneously. Further, it comes with a digital hour meter, which helps track maintenance intervals and runtime, ensuring that the generator remains in optimal working condition.

Safety is a priority with the 005220-0, as it incorporates low-oil shutdown technology, which automatically turns off the engine when oil levels are dangerously low. This feature prevents potential engine damage, extending the lifespan of the generator. Additionally, it is equipped with a circuit breaker, protecting against overloads, thereby safeguarding both the generator and connected devices.

One of the key characteristics of the Generac 005220-0 is its portability. The generator is designed with a sturdy frame and comes with never-flat wheels and a folding handle, making it easy to transport to various locations as needed.

In summary, the Generac 005220-0 stands out for its powerful performance, extended runtime, user-friendly features, and safety attributes. Whether for home backup or job site power, it provides confidence and reliability, ensuring that power needs are met even in challenging circumstances.