Standby Generator Sets Engine Protective Devices

ENGINE PROTECTIVE DEVICES

The standby generator may be required to operate for long periods of time without an operator on hand to monitor such engine conditions as coolant tempera- ture, oil pressure or rpm. For that reason, the engine has several devices designed to protect it against potentially damaging conditions by automatically shutting down the unit when the oil pressure is too low, the coolant temperature is too high, the coolant level is too low, or the engine is running too fast.

NOTE:

Engine protective switches and sensors are men- tioned here for the reader’s convenience. Also refer to the applicable control panel manual for additional automatic engine shutdown informa- tion.

‹HIGH COOLANT TEMPERATURE SWITCH

This switches contacts close if the temperature should exceed approximately 140° C (284° F), initiating an engine shutdown. The generator will automatically restart and the LED will reset once the temperature has returned to a safe operating level.

‹LOW COOLANT LEVEL SENSOR

Should the engine coolant level drop below the level of the high coolant temperature switch, it is possible for the engine to overheat without automatic shut- down. To prevent such overheating, the engine has a low coolant level sensor. If the level of engine coolant drops below the level of the low coolant level sensor, the engine automatically shuts down.

‹OVERCRANK SHUTDOWN

After a prespecified duration of cranking, this func- tion ends the cranking if the engine has failed to start. The overcrank LED will turn ON. Turn OFF the AUTO/OFF/MANUAL switch, then turn switch back to AUTO to reset the generator control board.

NOTE:

If the fault is not corrected, the overcrank feature will continue to activate.

Approximate Crank Cycle Times

15 seconds ON

7 seconds OFF

7 seconds ON

7 seconds OFF

Repeat for 45 seconds Approximately 90 seconds total.

‹OVERSPEED SHUTDOWN

A speed circuit controls engine cranking, start-up, operation and shutdown. Engine speed signals are delivered to the circuit board whenever the unit is running. Should the engine overspeed above a safe, preset value, the circuit board initiates an automatic engine shutdown. Contact the nearest Authorized Dealer if this failure occurs.

‹RPM SENSOR LOSS SHUTDOWN

If the speed signal to the control panel is lost, engine shutdown will occur.

‹LOW OIL PRESSURE SWITCH

This switch has normally closed contacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below the 8 psi range, switch contacts close, and the engine shuts down. The unit should not be restarted until oil is added, and the AUTO/OFF/MANUAL switch must be turned to OFF and then back to AUTO.

‹DC FUSE

This fuse is located inside of the control panel. It protects the panel wiring and components from damaging overload. Always remove this fuse before commencing work on the generator. The unit will not start or crank if the fuse is blown. Replace the fuse with one of the same size, type, and rating. (See the exploded views and parts lists at the end of this manual for replacement part number.)

4-1

08/05

0 .Rev EngProt001

Page 8
Image 8
Generac Power Systems 1.6L 18 kW owner manual Engine Protective Devices

1.6L 18 kW specifications

Generac Power Systems has established itself as a leader in providing reliable, high-performance energy solutions, particularly known for its innovative generators. Among its impressive lineup, the Generac 1.6L 18 kW generator stands out for residential and light commercial applications. This robust generator is designed to deliver dependable power during outages, ensuring peace of mind for homeowners and businesses alike.

One of the defining features of the Generac 1.6L 18 kW generator is its powerful engine, engineered for performance and durability. With an 18 kW output, it is capable of powering essential household appliances, heating and cooling systems, and other necessary equipment. The generator’s advanced design includes an efficient 1.6L engine, which not only contributes to its high power output but also optimizes fuel consumption, providing a sustainable energy solution.

The generator is equipped with Generac's True Power Technology, which offers clean, stable power with low Total Harmonic Distortion (THD). This is crucial for protecting sensitive electronics and appliances from potential damage caused by power fluctuations. With this technology, users can operate delicate devices like computers and medical equipment without concerns about power integrity.

Another significant advantage of the Generac 1.6L 18 kW generator is its integrated Automatic Transfer Switch (ATS). This feature automatically detects power outages and switches the generator on within seconds, ensuring that users remain connected and protected during electrical disruptions. The ATS not only enhances reliability but also allows for seamless integration with existing electrical systems.

In terms of design, the Generac 1.6L 18 kW generator boasts a compact footprint, making it suitable for various installation options, including outdoor placements with adequate ventilation. Additionally, its quiet operation is an attractive feature for residential settings, minimizing noise pollution while maintaining performance.

The generator is user-friendly, with an intuitive control panel that provides real-time monitoring and diagnostics. This ensures that users can easily manage their power needs and keep track of the generator’s performance.

In conclusion, the Generac Power Systems 1.6L 18 kW generator offers a powerful, efficient, and dependable energy solution. With its advanced technology, automatic transfer capabilities, and user-friendly design, it effectively addresses the power demands of both homes and light commercial buildings, making it an excellent choice for those seeking uninterrupted energy supply.