Standby Generator Sets

Troubleshooting

TROUBLESHOOTING GUIDE

PROBLEM

CAUSE

CORRECTION

Engine won’t crank.

1.

15 amp fuse blown.

1.

Replace fuse.

 

2.

Loose or corroded or defective

2.

Tighten, clean or replace

 

 

battery cables.

 

battery cables as necessary.

 

3.

Defective starter contactor.

3.

Replace contactor.*

 

4.

Defective starter motor.

4.

Replace starter motor.*

 

5.

Dead or Defective Battery.

5.

Remove, change or replace battery.

 

6.

5 amp fuse blown.

6.

Replace fuse.*

 

 

 

 

 

Engine cranks but won't start

1.

Out of fuel.

1.

Replenish fuel.

 

2.

Fuel solenoid (FS) is defective

2.

Replace solenoid.*

 

3.

Open Wire #14A from Engine Control

3.

Reconnect wire.

 

 

circuit board.

 

 

 

4.

Spark plugs defective.

4.

Clean, regap or replace plugs.

 

5.

Door on tank not closed.

5.

Close door on tank.

Engine starts hard, runs rough.

1.Flame arrestor (air cleaner) plugged or damaged.

2.Plugged fuel line.

3.Defective spark plugs.

4.Fuel pressure incorrect.

1.Clean or replace as needed.

2.Unclog fuel line.

3.Clean, regap or replace plugs.

4.Confirm fuel pressure to regulator is as recommended in SPECIFICATIONS.

Engine starts then shuts down.

1.

Engine oil level is low.

1.

Check oil and add oil as needed.

 

2.

Engine is overheated.

2.

Check cooling system for leaks.

 

3.

Defective Low Oil Pressure Switch

3.

Replace switch.*

 

4.

Defective Coolant Temperature Switch

4.

Replace switch.*

 

5.

Defective Control Module circuit board.

5.

Replace board.*

 

6.

Coolant Level is Low.

6.

Repair leak - Add coolant.

 

7.

Defective Low Coolant Level Switch

7.

Replace Switch.*

 

 

 

 

 

AUTO/OFF/MANUAL Switch at OFF,

1.

Defective AUTO/OFF/MANUAL switch

1.

Replace switch.*

engine continues to run

2.

Open/disconnected wire #15A between

2.

Reconnect/close wire.

 

 

AUTO/OFF/MANUAL switch and Control

 

 

 

 

Module circuit board.

 

 

 

3.

Defective Control Module circuit board

3.

Replace board.*

 

 

 

 

 

No AC output from generator.

1.

Check main line circuit breaker.

1.

Reset to ON or CLOSED.

 

2.

Check circuit breaker & fuses.

2.

Reset and replace, if necessary.

 

3.

Transfer switch set to NORMAL position

3.

Set to GENERATOR position.

 

4.

Generator internal failure.

4.

*

 

5.

Thermal circuit breaker open.

5.

Auto-reset - Wait 5 min. and

 

 

 

 

attempt restart.

*Contact the nearest Dealer for assistance.

12-1

09/05

0 .Rev Trblsht002

Page 23
Image 23
Generac Power Systems 1.6L 18 kW owner manual Troubleshooting Guide, Problem Cause Correction

1.6L 18 kW specifications

Generac Power Systems has established itself as a leader in providing reliable, high-performance energy solutions, particularly known for its innovative generators. Among its impressive lineup, the Generac 1.6L 18 kW generator stands out for residential and light commercial applications. This robust generator is designed to deliver dependable power during outages, ensuring peace of mind for homeowners and businesses alike.

One of the defining features of the Generac 1.6L 18 kW generator is its powerful engine, engineered for performance and durability. With an 18 kW output, it is capable of powering essential household appliances, heating and cooling systems, and other necessary equipment. The generator’s advanced design includes an efficient 1.6L engine, which not only contributes to its high power output but also optimizes fuel consumption, providing a sustainable energy solution.

The generator is equipped with Generac's True Power Technology, which offers clean, stable power with low Total Harmonic Distortion (THD). This is crucial for protecting sensitive electronics and appliances from potential damage caused by power fluctuations. With this technology, users can operate delicate devices like computers and medical equipment without concerns about power integrity.

Another significant advantage of the Generac 1.6L 18 kW generator is its integrated Automatic Transfer Switch (ATS). This feature automatically detects power outages and switches the generator on within seconds, ensuring that users remain connected and protected during electrical disruptions. The ATS not only enhances reliability but also allows for seamless integration with existing electrical systems.

In terms of design, the Generac 1.6L 18 kW generator boasts a compact footprint, making it suitable for various installation options, including outdoor placements with adequate ventilation. Additionally, its quiet operation is an attractive feature for residential settings, minimizing noise pollution while maintaining performance.

The generator is user-friendly, with an intuitive control panel that provides real-time monitoring and diagnostics. This ensures that users can easily manage their power needs and keep track of the generator’s performance.

In conclusion, the Generac Power Systems 1.6L 18 kW generator offers a powerful, efficient, and dependable energy solution. With its advanced technology, automatic transfer capabilities, and user-friendly design, it effectively addresses the power demands of both homes and light commercial buildings, making it an excellent choice for those seeking uninterrupted energy supply.