Generac Power Systems COMMERCIAL SERIES manual Operating Data, COMMERCIAL 60 kW

Models: COMMERCIAL SERIES

1 4
Download 4 pages 15.77 Kb
Page 3
Image 3
OPERATING DATA

COMMERCIAL 60 kW

COMMERCIAL SERIES

OPERATING DATA

 

 

 

COMMERCIAL 60 kW

 

KW RATING

 

 

60

 

 

 

 

 

 

ENGINE SIZE

 

 

3.0 Liter V-6

 

 

 

 

 

 

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

 

KW

AMP

CB Size

120/240V, single phase, 1.0 pf

 

60

250

300

120/208V, 3-phase, 0.8 pf

 

60

208.4

250

120/240V, 3-phase, 0.8 pf

 

60

180.6

200

277/480V, 3-phase, 0.8 pf

 

60

90.3

100

 

 

 

 

 

GENERATOR LOCKED ROTOR KVA

 

 

 

 

AVAILABLE @ VOLTAGE DIP OF 35%

 

 

 

 

Single phase or 208V & 240V 3-phase

 

 

120

 

480V 3-phase

 

 

141

 

 

 

 

 

 

ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)

 

Natural Gas

 

Propane

 

 

(ft3/hr.)

(gal/hr.)

cu ft/hr

Exercise cycle

 

123

1.34

48.7

25% of rated load

 

260

2.84

103.3

50% of rated load

 

500

5.46

198.6

75% of rated load

 

700

7.64

277.9

100% of rated load

 

960

10.48

381.3

 

 

 

 

 

ENGINE COOLING

ft3/min.

 

 

 

Air flow (inlet air including alternator and combustion air)

 

3,280

 

System coolant capacity

US gal.

 

2.5

 

Heat rejection to coolant

BTU/hr.

 

270,000

 

Max. operating air temp. on radiator

°C (°F)

 

60 (150)

 

Max. ambient temperature

°C (°F)

 

50 (140)

 

 

 

 

 

 

COMBUSTION AIR REQUIREMENTS

 

 

 

 

Flow at rated power 60 Hz

cfm

 

180

 

 

 

 

 

 

SOUND EMISSIONS IN DBA

 

 

 

 

db(A) @ 23 feet in exercise mode

 

 

63

 

db(A) @ 23 feet at normal operating load

 

 

71

 

 

 

 

 

 

EXHAUST

 

 

 

 

Exhaust flow at rated output 60 Hz

cfm

 

494

 

Exhaust temp. at muffler outlet

°F

 

1,050

 

 

 

 

 

 

ENGINE PARAMETERS

 

 

 

 

Rated synchronous RPM

60 Hz

 

3600

 

HP at rated KW

60 Hz

 

94

 

 

 

 

 

 

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

 

 

 

 

Temperature Deration

 

 

 

 

3% for every 10 °C above - °C

 

25

 

1.65% for every 10 °F above - °F

 

77

 

Altitude Deration

 

 

 

 

1% for every 100 m above - m

 

183

 

3% for every 1000 ft. above - ft.

 

600

 

 

 

 

 

 

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.

Page 3
Image 3
Generac Power Systems COMMERCIAL SERIES manual Operating Data, COMMERCIAL 60 kW