Goodman Mfg CKF50Hz, Condensing Units service manual Performance Data, Performance Test

Models: CKF50Hz Condensing Units

1 21
Download 21 pages 5.36 Kb
Page 19
Image 19

PERFORMANCE DATA

PERFORMANCE TEST

All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets:

If conditions vary from this, results will change as follows:

1.As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and high side pressures and power will not change.

2.As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will occur in low and high side pressures and power.

A properly operating unit should be within plus or minus 2 degrees of the subcooling value shown in the installation instructions.

A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.

A properly operating unit should be within plus or minus 10 PSIG of the HI PR shown.

A properly operating unit should be within plus or minus 5 PSIG of the LO PR shown.

A properly operating unit should be within plus or minus 3 Amps of the typical value shown.

19

Page 19
Image 19
Goodman Mfg CKF50Hz, Condensing Units service manual Performance Data, Performance Test