PRODUCT DESIGN

Thermostats:

NOTE: Complete lineup of thermostats can be found in the Thermostat Specification Sheets.

Filters:

Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty.

Upflow Filters

This furnace has provisions for the installation of return air filters at the side and/or bottom return. The furnace will accommodate the following filter sizes depending on cabinet size:

SIDE RETURN

 

Cabinet

Nominal

Approx.

 

 

Width

Filter Size

Flow Area

 

 

(in.)

(in.)

(in2)

 

 

 

 

 

 

 

All

16 x 25 x 1

400

 

 

 

 

 

 

BOTTOM RETURN

Cabinet

Nominal

Approx.

Width

Filter Size

Flow Area

(in.)

(in.)

(in2)

 

 

 

17-1/2

14 x 25 x 1

350

21

16 x 25 x 1

400

24-1/2

20 x 25 x 1

500

 

 

 

Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in the duct system such as a central return.

 

 

COOLING AIRFLOW REQUIREMENT (CFM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

800

1000

1200

1400

1600

2000

 

 

 

 

 

 

 

 

 

 

0453_X*

376*

384

480

576

---

---

---

 

 

 

 

 

 

 

 

 

Airflow

0703_X*

---

564*

564*

564*

672

---

---

 

 

 

 

 

 

 

 

0704_X*

---

---

564*

564*

672

768

---

 

 

 

 

 

 

 

 

 

 

Input

0904_X*

---

---

752*

752*

752*

768

---

 

 

 

 

 

 

 

 

0905_X*

---

---

---

752*

752*

768

800

 

 

 

 

 

 

 

 

 

 

 

1155_X*

---

---

---

940*

940*

940*

800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Minimum filter area dictated by heating airflow requirement.

 

 

 

 

 

 

 

 

 

 

 

COOLING AIRFLOW REQUIREMENT (CFM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

800

1000

1200

1400

1600

2000

 

 

 

 

 

 

 

 

 

 

0453_X*

188*

192

240

288

---

---

---

 

 

 

 

 

 

 

 

 

Airflow

0703_X*

---

282*

282*

282*

336

---

---

 

 

 

 

 

 

 

 

0704_X*

---

---

260*

260*

336

384

---

 

 

 

 

 

 

 

 

 

 

Input

0904_X*

---

---

376*

376*

376*

384

---

 

 

 

 

 

 

 

 

0905_X*

---

---

---

376*

376*

384

480

 

 

 

 

 

 

 

 

 

 

 

115_X*

---

---

---

470*

470*

470*

480

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Minimum filter area dictated by heating airflow requirement.

Disposable Minimum Filter Area (in2)

Permanent Minimum Filter Area (in2)

[Based on a 300 ft/min filter face velocity]

[Based on 600 ft/min filter face velocity]