APPENDIX A BLOWER PERFORMANCE TABLES
DIRECT DRIVE
STANDARD CPC/H060 DOWN SHOT
CPC/H060 DIRECT DRIVE DOWN SHOT
SPEED | EXTERNAL STATIC | STANDARD | AMPS | WATTS | RPM | |
PRESSURE (ESP) | ||||||
TAP | CFM | |||||
in w.c. |
|
|
| |||
|
|
|
|
| ||
|
|
|
|
|
| |
| 0.10 | 1334 | 1.65 | 180 | 627 | |
| 0.20 | 1286 | 1.75 | 192 | 665 | |
| 0.30 | 1212 | 1.83 | 202 | 715 | |
| 0.40 | 1144 | 1.94 | 216 | 759 | |
T1 | 0.50 | 1077 | 1.99 | 222 | 792 | |
| 0.60 | 1039 | 2.10 | 238 | 830 | |
| 0.70 | 953 | 2.17 | 248 | 874 | |
| 0.80 | 904 | 2.27 | 258 | 913 | |
| 0.90 | 825 | 2.30 | 266 | 940 | |
| 0.10 | 1512 | 2.12 | 240 | 682 | |
| 0.20 | 1469 | 2.24 | 254 | 720 | |
| 0.30 | 1397 | 2.31 | 264 | 759 | |
| 0.40 | 1333 | 2.44 | 282 | 803 | |
T2 | 0.50 | 1285 | 2.54 | 296 | 836 | |
| 0.60 | 1221 | 2.59 | 304 | 874 | |
| 0.70 | 1173 | 2.72 | 322 | 913 | |
| 0.80 | 1118 | 2.77 | 328 | 946 | |
| 0.90 | 1049 | 2.90 | 344 | 984 | |
| 0.10 | 2053 | 4.27 | 540 | 869 | |
| 0.20 | 2014 | 4.39 | 558 | 896 | |
| 0.30 | 1999 | 4.60 | 576 | 929 | |
T3 | 0.40 | 1947 | 4.68 | 588 | 957 | |
0.50 | 1897 | 4.79 | 608 | 989 | ||
| 0.60 | 1857 | 4.87 | 620 | 1012 | |
| 0.70 | 1763 | 4.99 | 640 | 1050 | |
| 0.80 | 1741 | 5.06 | 650 | 1072 | |
| 0.90 | 1669 | 5.19 | 668 | 1105 | |
| 0.10 | 2137 | 4.95 | 634 | 913 | |
| 0.20 | 2093 | 5.07 | 652 | 940 | |
| 0.30 | 2095 | 5.19 | 670 | 962 | |
| 0.40 | 2026 | 5.28 | 682 | 990 | |
T4 | 0.50 | 1980 | 5.40 | 698 | 1018 | |
| 0.60 | 1961 | 5.49 | 720 | 1039 | |
| 0.70 | 1914 | 5.58 | 732 | 1072 | |
| 0.80 | 1845 | 5.70 | 742 | 1100 | |
| 0.90 | 1766 | 5.69 | 740 | 1127 | |
| 0.10 | 2299 | 5.70 | 742 | 942 | |
| 0.20 | 2233 | 5.80 | 748 | 969 | |
| 0.30 | 2217 | 5.90 | 768 | 990 | |
| 0.40 | 2157 | 6.07 | 786 | 1018 | |
T5 | 0.50 | 2131 | 6.12 | 804 | 1045 | |
| 0.60 | 2060 | 6.21 | 816 | 1073 | |
| 0.70 | 2015 | 6.30 | 820 | 1095 | |
| 0.80 | 1940 | 6.27 | 816 | 1111 | |
| 0.90 | 1862 | 6.13 | 790 | 1128 |
NOTES:
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %. 5 Ton models are shipped from the factory with speed tap set on T4.