Goodman Mfg 3 Ton- 6 Ton CPC/CPH Series installation instructions STANDARD CPC/H060 DOWN SHOT

Models: 3 Ton- 6 Ton CPC/CPH Series Light Commercial Self-Contained Packaged Heating & Cooling Unit

1 28
Download 28 pages 12.09 Kb
Page 19
Image 19

APPENDIX A BLOWER PERFORMANCE TABLES

DIRECT DRIVE

STANDARD CPC/H060 DOWN SHOT

CPC/H060 DIRECT DRIVE DOWN SHOT

SPEED

EXTERNAL STATIC

STANDARD

AMPS

WATTS

RPM

PRESSURE (ESP)

TAP

CFM

in w.c.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.10

1334

1.65

180

627

 

0.20

1286

1.75

192

665

 

0.30

1212

1.83

202

715

 

0.40

1144

1.94

216

759

T1

0.50

1077

1.99

222

792

 

0.60

1039

2.10

238

830

 

0.70

953

2.17

248

874

 

0.80

904

2.27

258

913

 

0.90

825

2.30

266

940

 

0.10

1512

2.12

240

682

 

0.20

1469

2.24

254

720

 

0.30

1397

2.31

264

759

 

0.40

1333

2.44

282

803

T2

0.50

1285

2.54

296

836

 

0.60

1221

2.59

304

874

 

0.70

1173

2.72

322

913

 

0.80

1118

2.77

328

946

 

0.90

1049

2.90

344

984

 

0.10

2053

4.27

540

869

 

0.20

2014

4.39

558

896

 

0.30

1999

4.60

576

929

T3

0.40

1947

4.68

588

957

0.50

1897

4.79

608

989

 

0.60

1857

4.87

620

1012

 

0.70

1763

4.99

640

1050

 

0.80

1741

5.06

650

1072

 

0.90

1669

5.19

668

1105

 

0.10

2137

4.95

634

913

 

0.20

2093

5.07

652

940

 

0.30

2095

5.19

670

962

 

0.40

2026

5.28

682

990

T4

0.50

1980

5.40

698

1018

 

0.60

1961

5.49

720

1039

 

0.70

1914

5.58

732

1072

 

0.80

1845

5.70

742

1100

 

0.90

1766

5.69

740

1127

 

0.10

2299

5.70

742

942

 

0.20

2233

5.80

748

969

 

0.30

2217

5.90

768

990

 

0.40

2157

6.07

786

1018

T5

0.50

2131

6.12

804

1045

 

0.60

2060

6.21

816

1073

 

0.70

2015

6.30

820

1095

 

0.80

1940

6.27

816

1111

 

0.90

1862

6.13

790

1128

NOTES:

Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %. 5 Ton models are shipped from the factory with speed tap set on T4.

19

Page 19
Image 19
Goodman Mfg 3 Ton- 6 Ton CPC/CPH Series STANDARD CPC/H060 DOWN SHOT, Appendix A Blower Performance Tables Direct Drive