Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit

Models: 3 Ton- 6 Ton CPC/CPH Series Light Commercial Self-Contained Packaged Heating & Cooling Unit

1 28
Download 28 pages 12.09 Kb
Page 24
Image 24

APPENDIX A BLOWER PERFORMANCE TABLES

BELT DRIVE

HIGH STATIC HORIZONTAL

CPC/H036 HIGH STATIC BELT DRIVE HORIZONTAL

ESP, In

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

0

 

1

 

2

 

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

1742

 

0.50

1431

 

0.36

0.8

 

 

 

 

 

 

 

 

 

 

1626

 

0.52

1357

 

0.39

1078

 

0.27

1

 

 

 

 

 

 

 

1611

 

0.56

1315

 

0.42

1011

 

0.28

 

 

 

1.2

 

 

 

 

1605

 

0.62

1299

 

0.46

976

 

0.31

 

 

 

 

 

 

1.4

 

1605

 

0.68

1281

 

0.51

959

 

0.35

 

 

 

 

 

 

 

 

 

1.6

 

1281

 

0.57

981

 

0.41

 

 

 

 

 

 

 

 

 

 

 

 

1.8

 

981

 

0.47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPC/H048 HIGH STATIC BELT DRIVE HORIZONTAL

ESP, In

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

0

 

1

 

2

 

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

2056

 

0.72

1721

 

0.54

0.8

 

 

 

 

 

 

 

 

 

 

1996

 

0.77

1662

 

0.57

1328

 

0.40

1

 

 

 

 

 

 

 

1924

 

0.79

1603

 

0.61

1270

 

0.43

 

 

 

1.2

 

 

 

 

1952

 

0.88

1559

 

0.64

1210

 

0.44

 

 

 

 

 

 

1.4

 

1888

 

0.92

1543

 

0.70

1195

 

0.49

 

 

 

 

 

 

 

 

 

1.6

 

1557

 

0.77

1180

 

0.54

 

 

 

 

 

 

 

 

 

 

 

 

1.8

 

1192

 

0.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPC/H060 HIGH STATIC BELT DRIVE HORIZONTAL

ESP, In

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

 

0

1

 

2

 

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2323

 

0.92

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

2315

 

1.00

2009

 

0.77

1

 

 

 

 

 

 

 

 

 

 

2308

 

1.09

1992

 

0.84

1666

 

0.60

1.2

 

 

 

 

 

 

 

2338

 

1.21

1992

 

0.92

1646

 

0.66

 

 

 

1.4

 

 

 

 

2359

 

1.32

2025

 

1.02

1648

 

0.72

 

 

 

 

 

 

1.6

 

2404

 

1.45

2056

 

1.13

1684

 

0.82

 

 

 

 

 

 

 

 

 

1.8

 

2088

 

1.24

1722

 

0.92

 

 

 

 

 

 

 

 

 

 

 

 

CPC/H072 HIGH STATIC BELT DRIVE HORIZONTAL

ESP, In

 

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

0

 

1

 

 

2

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

2746

 

1.38

2515

 

1.12

0.8

 

 

 

 

 

 

 

 

 

 

2721

 

1.47

2494

 

1.21

2261

 

0.97

1

 

 

 

 

 

 

 

2689

 

1.56

2500

 

1.32

2255

 

1.06

1994

 

0.83

1.2

 

 

 

 

2752

 

1.74

2473

 

1.40

2252

 

1.15

1996

 

0.91

 

 

 

1.4

 

2802

 

1.88

2487

 

1.53

2286

 

1.27

2037

 

1.02

 

 

 

 

 

 

1.6

 

2553

 

1.67

2308

 

1.40

1997

 

1.08

 

 

 

 

 

 

 

 

 

1.8

 

2355

 

1.51

2014

 

1.19

 

 

 

 

 

 

 

 

 

 

 

 

2.0

 

2055

 

1.29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.

24

Page 24
Image 24
Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit High Static Horizontal