Goodman Mfg RS6300011 service manual Package Cooling Specifications, GPC1436-42H41AA

Models: GPC 14 SEER R-410 Package Air Conditioners with R-410A RS6300011

1 43
Download 43 pages 51.79 Kb
Page 12
Image 12

PACKAGE COOLING SPECIFICATIONS

GPC14[36-42]H41AA

 

 

 

 

 

 

 

 

 

GPC1436H41*

GPC1442H41*

 

 

 

 

 

 

 

 

COOLING

COOLING CAPACITY, BTUH

35,600

40,000

 

 

CAPACITY

SEER / EER

14.0 / 12.0

14.2/ 12.0

 

 

 

 

 

 

 

 

UNIT

VOLTAGE (NAMEPLATE)

208-230/1/60

208-230/1/60

 

 

ELECTRICAL

AMPS (TOTAL)

20.06

22.2

 

 

SPECIFICATION

MINIMUM CIRCUIT AMPACITY

24.2

26.6

 

 

 

MAXIMUM OVERCURRENT PROTECTION (1)

40

40

 

 

COMPRESSOR

TYPE

SCROLL

SCROLL

 

 

 

RATED LOAD AMPS

16.7

17.9

 

 

 

LOCKED ROTOR AMPS

79

112

 

 

 

 

 

 

 

 

CONDENSER

HORSEPOWER

1/4

1/4

 

 

FAN MOTOR

RPM

830

1075

 

 

 

FULL LOAD AMPS

1.5

1.4

 

 

 

LOCKED ROTOR AMPS

3.0

2.9

 

 

CONDENSER FAN

BLADE DIAMETER (INCHES) / # OF BLADES

22 / 3

22 / 4

 

 

CONDENSER

FACE AREA - SQ. FT.

13.4

17.0

 

 

COIL

NUMBER OF ROWS

1

1

 

 

 

FINS PER INCH

24

24

 

 

 

 

 

 

 

 

EVAPORATOR

HORSEPOWER - NO. OF SPEEDS

1/2 - 5

1/2 - 5

 

 

BLOWER

FULL LOAD AMPS

1.86

2.9

 

 

MOTOR

LOCKED ROTOR AMPS

NA

NA

 

 

 

MOTOR SPEED TAP - COOLING

T2

T2

 

 

 

RPM

1050

1050

 

 

 

 

 

 

 

 

EVAPORATOR

DIAMETER X WIDTH (INCHES)

10 X 8

10 x 8

 

 

BLOWER

HI EFFICIENCY COOLING CFM

1,200

1,300

 

 

 

5 TON NOMINAL COOLING CFM

NA

NA

 

 

 

FAN ONLY COOLING CFM

1,100

1,200

 

 

 

MAX EXTERNAL STATIC PRESS ("w.c.)

0.5

0.5

 

 

 

 

 

 

 

 

EVAPORATOR

FACE AREA - SQ. FT.

5.2

6.2

 

 

COIL

NUMBER OF ROWS

3

4

 

 

 

FINS PER INCH

14

14

 

 

 

 

 

 

 

 

GENERAL

FILTER SIZE - SQ. FT. *

25 x 25 x 1

(2) 20 x 20 x 1

 

 

INFORMATION

DRAIN SIZE (INCHES)

3/4"

3/4"

 

 

 

EXPANSION DEVICE

ORIFICE (0.065)

ORIFICE (0.072)

 

 

 

REFRIGERANT CHARGE R-410A (Oz.)

80

118

 

 

 

POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN

3/4, 1, 1-1/4

3/4, 1, 1-1/4

 

 

 

LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)

1/2

1/2

 

 

 

SHIPPING WEIGHT LBS.

370

370

 

 

 

OPERATING WEIGHT LBS.

360

360

 

 

 

 

 

 

 

(1)Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. * Calculated external filter size based on air velocity of 300 ft/min.

Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.

IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.