GPC14[24-60]H41A*

PRODUCT DESIGN

 

 

GPC14[24-60]H41A*

HKR ELECTRICAL DATA

 

 

 

 

 

 

 

 

 

 

 

Circuit #1

Circuit #2

 

Model and Heat Kit Usage

Minimum Circuit

 

Maximum

Minimum Circuit

Maximum

Actual

 

Overcurrent

Overcurrent

kW & BTU

Ampacity

 

Ampacity

 

 

Protection (amps)

Protection (amps)

at 240V

 

at 208 / 240V

 

at 208 / 240V

 

 

at 208 / 240V

at 208 / 240V

 

 

 

 

 

 

GPH1424H41A*

 

 

 

 

 

 

HKR05*,C*

24 / 27

 

30 / 30

----

----

4.75 / 16,200

HKR08*,C*

33 / 28

 

40 / 40

----

----

7.00 / 23,800

HKR10*,C*

45 / 51

 

60 / 60

----

----

9.50 / 32,400

GPH1430H41A*

 

 

 

 

 

 

HKR05*,C*

24 / 27

 

30 / 30

----

----

4.75 / 16,200

HKR08*,C*

34 / 39

 

40 / 40

----

----

7.00 / 23,800

HKR10*,C*

45 / 52

 

60 / 60

----

----

9.50 / 32,400

HKR15*,C*

45 / 52

 

60 / 60

22 / 25

30 / 30

14.25 / 48,600

GPH1436H41A*

 

 

 

 

 

 

HKR05*,C*

24 / 27

 

30 / 30

----

----

4.75 / 16,200

HKR08*,C*

34 / 39

 

40 / 40

----

----

7.00 / 23,800

HKR10*,C*

45 / 52

 

60 / 60

----

----

9.50 / 32,400

HKR15*,C*

45 / 52

 

60 / 60

22 / 25

30 / 30

14.25 / 48,600

GPH1442H41A*

 

 

 

 

 

 

HKR05*,C*

25 / 27

 

30 / 30

----

----

4.75 / 16,200

HKR08*,C*

34 / 39

 

40 / 40

----

----

7.00 / 23,800

HKR10*,C*

46 / 52

 

60 / 60

----

----

9.50 / 32,400

HKR15*,C*

46 / 52

 

60 / 60

22 / 25

30 / 30

14.25 / 48,600

HKR20*,C*

46 / 52

 

60 / 60

43 / 49

60 / 60

19.50 / 66,500

GPH1448H41A*

 

 

 

 

 

 

HKR05*,C*

25 / 28

 

30 / 30

----

----

4.75 / 16,200

HKR08*,C*

34 / 40

 

40 / 40

----

----

7.00 / 23,800

HKR10*,C*

46 / 53

 

60 / 60

----

----

9.50 / 32,400

HKR15*,C*

46 / 52

 

60 / 60

22 / 25

30 / 30

14.25 / 48,600

HKR20*,C*

46 / 52

 

60 / 60

43 / 49

60 / 60

19.50 / 66,500

GPH1460H41A*

 

 

 

 

 

 

HKR05*,C*

26 / 30

 

30 / 30

----

----

4.75 / 16,200

HKR08*,C*

36 / 40

 

40 / 40

----

----

7.00 / 23,800

HKR10*,C*

48 / 54

 

60 / 60

----

----

9.50 / 32,400

HKR15*,C*

48 / 54

 

60 / 60

22 / 25

30 / 30

14.25 / 48,600

HKR20*,C*

48 / 54

 

60 / 60

43 / 49

60 / 60

19.50 / 66,500

IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.

All wires and overcurrent protection devices are sized for use with electric heaters only and without WARNING refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent

protection during refrigeration cycle.

7

Page 7
Image 7
Goodman Mfg GPC 14 SEER R-410 Package Air Conditioners with R-410A Hkr Electrical Data, GPC1424-60H41A, Product Design