PRODUCT DESIGN |
|
|
| |||
HKR ELECTRICAL DATA |
|
|
|
| ||
|
|
|
|
|
| |
| Circuit #1 | Circuit #2 |
| |||
Model and Heat Kit Usage | Minimum Circuit |
| Maximum | Minimum Circuit | Maximum | Actual |
| Overcurrent | Overcurrent | kW & BTU | |||
Ampacity |
| Ampacity | ||||
|
| Protection (amps) | Protection (amps) | at 240V | ||
| at 208 / 240V |
| at 208 / 240V | |||
|
| at 208 / 240V | at 208 / 240V |
| ||
|
|
|
|
| ||
GPH1424H41A* |
|
|
|
|
|
|
HKR05*,C* | 24 / 27 |
| 30 / 30 | 4.75 / 16,200 | ||
HKR08*,C* | 33 / 28 |
| 40 / 40 | 7.00 / 23,800 | ||
HKR10*,C* | 45 / 51 |
| 60 / 60 | 9.50 / 32,400 | ||
GPH1430H41A* |
|
|
|
|
|
|
HKR05*,C* | 24 / 27 |
| 30 / 30 | 4.75 / 16,200 | ||
HKR08*,C* | 34 / 39 |
| 40 / 40 | 7.00 / 23,800 | ||
HKR10*,C* | 45 / 52 |
| 60 / 60 | 9.50 / 32,400 | ||
HKR15*,C* | 45 / 52 |
| 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 |
GPH1436H41A* |
|
|
|
|
|
|
HKR05*,C* | 24 / 27 |
| 30 / 30 | 4.75 / 16,200 | ||
HKR08*,C* | 34 / 39 |
| 40 / 40 | 7.00 / 23,800 | ||
HKR10*,C* | 45 / 52 |
| 60 / 60 | 9.50 / 32,400 | ||
HKR15*,C* | 45 / 52 |
| 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 |
GPH1442H41A* |
|
|
|
|
|
|
HKR05*,C* | 25 / 27 |
| 30 / 30 | 4.75 / 16,200 | ||
HKR08*,C* | 34 / 39 |
| 40 / 40 | 7.00 / 23,800 | ||
HKR10*,C* | 46 / 52 |
| 60 / 60 | 9.50 / 32,400 | ||
HKR15*,C* | 46 / 52 |
| 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 |
HKR20*,C* | 46 / 52 |
| 60 / 60 | 43 / 49 | 60 / 60 | 19.50 / 66,500 |
GPH1448H41A* |
|
|
|
|
|
|
HKR05*,C* | 25 / 28 |
| 30 / 30 | 4.75 / 16,200 | ||
HKR08*,C* | 34 / 40 |
| 40 / 40 | 7.00 / 23,800 | ||
HKR10*,C* | 46 / 53 |
| 60 / 60 | 9.50 / 32,400 | ||
HKR15*,C* | 46 / 52 |
| 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 |
HKR20*,C* | 46 / 52 |
| 60 / 60 | 43 / 49 | 60 / 60 | 19.50 / 66,500 |
GPH1460H41A* |
|
|
|
|
|
|
HKR05*,C* | 26 / 30 |
| 30 / 30 | 4.75 / 16,200 | ||
HKR08*,C* | 36 / 40 |
| 40 / 40 | 7.00 / 23,800 | ||
HKR10*,C* | 48 / 54 |
| 60 / 60 | 9.50 / 32,400 | ||
HKR15*,C* | 48 / 54 |
| 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 |
HKR20*,C* | 48 / 54 |
| 60 / 60 | 43 / 49 | 60 / 60 | 19.50 / 66,500 |
IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.
All wires and overcurrent protection devices are sized for use with electric heaters only and without WARNING refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent
protection during refrigeration cycle.
7