Goodman Mfg GPC 14 SEER R-410 Package Air Conditioners with R-410A, RS6300011 service manual

Models: GPC 14 SEER R-410 Package Air Conditioners with R-410A RS6300011

1 43
Download 43 pages 51.79 Kb
Page 11
Image 11
PACKAGE COOLING SPECIFICATIONS GPC14[24-30]H41AA

PACKAGE COOLING SPECIFICATIONS GPC14[24-30]H41AA

 

 

GPC1424H41*

GPC1430H41*

 

 

 

 

COOLING

COOLING CAPACITY, BTUH

24,600

28,400

CAPACITY

SEER / EER

14.5 / 12.1

14.0 / 12.1

 

 

 

 

UNIT

VOLTAGE (NAMEPLATE)

208-230/1/60

208-230/1/60

ELECTRICAL

AMPS (TOTAL)

10.5

13.16

SPECIFICATION

MINIMUM CIRCUIT AMPACITY

12.5

15.6

 

MAXIMUM OVERCURRENT PROTECTION (1)

20

25

COMPRESSOR

TYPE

RECIP

RECIP

 

RATED LOAD AMPS

7.9

9.8

 

LOCKED ROTOR AMPS

41

55

 

 

 

 

CONDENSER

HORSEPOWER

1/6

1/4

FAN MOTOR

RPM

815

830

 

FULL LOAD AMPS

1.1

1.5

 

LOCKED ROTOR AMPS

1.7

3.0

 

 

 

 

CONDENSER FAN

BLADE DIAMETER (INCHES) / # OF BLADES

22 / 3

22 / 3

 

 

 

 

CONDENSER

FACE AREA - SQ. FT.

13.4

13.4

COIL

NUMBER OF ROWS

1

1

 

FINS PER INCH

24

24

EVAPORATOR

HORSEPOWER - NO. OF SPEEDS

1/2 - 5

1/2 - 5

BLOWER

FULL LOAD AMPS

1.5

1.86

MOTOR

LOCKED ROTOR AMPS

NA

NA

 

MOTOR SPEED TAP - COOLING

T2

T2

 

RPM

1050

1050

 

 

 

 

EVAPORATOR

DIAMETER X WIDTH (INCHES)

10 X 8

10 X 8

BLOWER

HI EFFICIENCY COOLING CFM

850

1,050

 

5 TON NOMINAL COOLING CFM

NA

NA

 

FAN ONLY COOLING CFM

800

950

 

MAX EXTERNAL STATIC PRESS ("w.c.)

0.5

0.5

 

 

 

 

EVAPORATOR

FACE AREA - SQ. FT.

5.25

5.25

COIL

NUMBER OF ROWS

3

3

 

FINS PER INCH

16

16

 

 

 

 

GENERAL

FILTER SIZE - SQ. FT. *

20 x 20 x 1

20 x 25 x 1

INFORMATION

DRAIN SIZE (INCHES)

3/4"

3/4"

 

EXPANSION DEVICE

ORIFICE (0.057)

ORIFICE (0.060)

 

REFRIGERANT CHARGE R-410A (Oz.)

83

78

 

POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN

3/4, 1, 1-1/4

3/4, 1, 1-1/4

 

LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)

1/2

1/2

 

SHIPPING WEIGHT LBS.

310

310

 

OPERATING WEIGHT LBS.

300

300

(1)Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. * Calculated external filter size based on air velocity of 300 ft/min.

Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.

IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.

11

Page 11
Image 11
Goodman Mfg GPC 14 SEER R-410 Package Air Conditioners with R-410A PACKAGE COOLING SPECIFICATIONS GPC1424-30H41AA