![BLOWER PERFORMANCE DATA](/images/new-backgrounds/89861/8986111x1.webp)
BLOWER PERFORMANCE DATA
HTR kW | MBVC1200* | MBVC1600* | MBVC2000* | SWITCH | SWITCH | SWITCH |
|
|
|
| 9 | 10 | 11 |
3 | 600 | 800 | 800 | ON | ON | ON |
5 | 600 | 800 | 800 | ON | ON | OFF |
6 | 635 | 800 | 800 | ON | OFF | ON |
8 | 740 | 1000 | 1000 | ON | OFF | OFF |
10 | 1000 | 1000 | 1200 | OFF | ON | ON |
15 | 1400 | 1500 | 1500 | OFF | ON | OFF |
20 | NR | NR | 2000 | OFF | OFF | ON |
21 | NR | NR | NR | ON^ | ON^ | ON^ |
^ Factory setting
| LOW STAGE | HIGH STAGE | COOL SELECTION | ADJUST SELECTION | PROFILE SELECTION | ||||
MODEL | SWITCHES | SWITCHES | SWITCHES | ||||||
COOL | COOL | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | |||
|
|
| |||||||
| 400 | 600 | OFF | OFF | OFF | OFF | OFF | OFF | |
MBVC1200 | 540 | 800 | ON | OFF | ON | OFF | ON | OFF | |
670 | 1000 | OFF | ON | OFF | ON | OFF | ON | ||
| |||||||||
| 800 | 1200 | ON | ON | ON | ON | ON | ON | |
| 670 | 1000 | OFF | OFF | OFF | OFF | OFF | OFF | |
MBVC1600 | 800 | 1200 | ON | OFF | ON | OFF | ON | OFF | |
940 | 1400 | OFF | ON | OFF | ON | OFF | ON | ||
| |||||||||
| 1070 | 1600 | ON | ON | ON | ON | ON | ON | |
| 800 | 1200 | OFF | OFF | OFF | OFF | OFF | OFF | |
MBVC2000 | 1070 | 1600 | ON | OFF | ON | OFF | ON | OFF | |
1200 | 1800 | OFF | ON | OFF | ON | OFF | ON | ||
| |||||||||
| 1340 | 2000 | ON | ON | ON | ON | ON | ON |
Locate the blower speed selection DIP switches on the integrated control module. Select the desired “cooling” speed tap by positioning switches 1 and 2 appropriately. Select the desired “adjust” tap by positioning switches 3 and 4 appropriately. Refer to the following figure for switch positions and their corresponding taps. Verify CFM by counting the number of times the green CFM LED blinks.
Normal* | +10% |
|
|
|
|
|
|
| Normal | |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OFF ON | OFF ON | OFF ON | OFF ON | |||||||||||||||||||||||||
3 |
|
|
|
|
| 3 |
|
|
|
|
|
|
| 3 |
|
|
|
|
|
|
| 3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
4 |
|
|
|
|
| 4 |
|
|
|
|
|
|
| 4 |
|
|
|
|
|
|
| 4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air flow Adjust Taps (*indicates factory setting)
Thermostat "Fan Only" Mode
During "Fan Only" operations, the CFM output is 30% of the maximum CFM capability.
CFM Trim Adjust
Minor adjustments can be made through the dipswitch combination of
6