Product Specifications
Product Specifications — CPC072 B Models
CPC072
XXX3BXXX
CPC072
XXX4BXXX
CPC072
XXX7BXXX
Cooling Capacity
Total BTU/h
Sensible BTU/h
EER
Decibels
AHRI Number
71,000 | 71,000 | 71,000 |
48,280 | 48,280 | 48,280 |
11.2 | 11.2 | 11.2 |
78.0 | 78.0 | 78.0 |
3397631 | 3397631 | 3397631 |
|
|
|
Evaporator Motor / Coil
Motor Type | Belt Drive | Belt Drive | Belt Drive |
|
|
|
|
Wheel (D x W) | 1 (11" x 10") | 1 (11" x 10") | 1 (11" x 10") |
|
|
|
|
Indoor Nominal CFM | 2,400 | 2,400 | 2,400 |
|
|
|
|
Indoor motor FLA (Cooling) | 5.0 | 2.5 | 2.3 |
|
|
|
|
Horsepower - RPM | |||
|
|
|
|
Piston Size (Cooling) | 0.094 | 0.094 | 0.094 |
|
|
|
|
Filter Size (Qty) | (4) 16" x 20" x 2" | (4) 16" x 20" x 2" | (4) 16" x 20" x 2" |
|
|
|
|
Drain Size (NPT) | ¾" | ¾" | ¾" |
|
|
|
|
213.0 | 213.0 | 213.0 | |
|
|
|
|
Evaporator Coil Face Area (ft²) | 8.9 | 8.9 | 8.9 |
|
|
|
|
Rows Deep/ Fins per Inch | 4/ 16 | 4/ 16 | 4/ 16 |
|
|
|
|
Motor Sheave | VL44 X 7/8 | VL44 X 7/8 | VL44 X 7/8 |
|
|
|
|
Blower Sheave | AK59 X 1 | AK59 X 1 | AK59 X 1 |
|
|
|
|
Belt | AX53 | AX53 | AX53 |
|
|
|
|
Condenser Fan / Coil |
|
|
|
|
|
|
|
Quantity of Condenser Fan Motors | 1 | 1 | 1 |
|
|
|
|
Horsepower - RPM | ⅓ - 1,075 | ⅓ - 1,075 | ⅓ - 1,075 |
|
|
|
|
Fan Diameter/ # Fan Blades | 22/ 4 | 22/ 4 | 22/ 4 |
|
|
|
|
Outdoor Nominal CFM | 4,300 | 4,300 | 4,300 |
|
|
|
|
Face Area (ft²) | 18.7 | 18.7 | 18.7 |
|
|
|
|
Rows Deep/ Fins per Inch | 2/ 20 | 2/ 20 | 2/ 20 |
|
|
|
|
Compressor |
|
|
|
|
|
|
|
Quantity / Type | 1 / Scroll | 1 / Scroll | 1 / Scroll |
|
|
|
|
Stage | Single | Single | Single |
|
|
|
|
Compressor RLA / LRA ea. | 19/123.0 | 9.7/62.0 | 7.4/50.0 |
|
|
|
|
Electrical Data |
|
|
|
|
|
|
|
Voltage/Phase/ Frequency | 460/3/60 | 575/3/60 | |
|
|
|
|
1.0 | 1.0 | 1.0 | |
|
|
|
|
Outdoor Fan FLA ea. | 1.90 | 1.20 | 0.90 |
|
|
|
|
Total Unit Amps | 25.9 | 13.4 | 10.6 |
|
|
|
|
Min. Circuit Ampacity¹ | 31 | 16 | 12 |
|
|
|
|
Max. Overcurrent Protection (amps)² | 45 | 25 | 15 |
|
|
|
|
Entrance Power Supply | 1.125" | 1.125” | 1.125” |
|
|
|
|
Entrance Control Voltage | ½" | ½" | ½" |
|
|
|
|
Operating Weight (lbs) | 640 | 640 | 640 |
|
|
|
|
Ship Weight (lbs) | 665 | 665 | 665 |
|
|
|
|
¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or
Note: Always check the S&R plate for electrical data on the unit being installed.
6 | www.goodmanmfg.com |