Goodman Mfg SS-CPC36-72 dimensions Product Specifications, kW Correction Factor

Models: SS-CPC36-72

1 36
Download 36 pages 30.91 Kb
Page 7
Image 7
kW Correction Factor

Product Specifications

Heat Kit Electrical Data (Blower Only, Heat Mode) — 3 Tons

Model and

MCA¹ at

MOP² (amps)

Actual kW &

Recommended

Heat Kit Usage

208 / 240V

at 208 / 240V

BTU at 240V

Airflow Range

CPC036***1D***

25

40

 

 

EHK1-10

48 / 55

50 / 60

10

1250-1350 CFM

EHK1-15

70 / 81

80 / 90

15

1400-1440 CFM

 

 

 

 

 

CPC036***3D***

17

25

 

 

EHK3-10

29 / 33

30 / 35

10

1250-1350 CFM

EHK3-15

42 / 48

45 / 50

15

1400-1440 CFM

 

 

 

 

 

CPC036***3B***

18

25

 

 

EHK3-10

30 / 33

35 / 35

10

1250-1350 CFM

EHK3-15

43 / 48

45 / 50

15

1400-1440 CFM

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW &

Recommended

Heat Kit Usage

at 480V

at 480V

BTU at 480V

Airflow Range

 

 

 

 

 

CPC036***4B***

10

15

 

 

EHK4-10

17

20

10

1250-1350 CFM

EHK4-15

25

25

15

1400-1440 CFM

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW &

Recommended

Heat Kit Usage

at 575V

at 575V

BTU at 575V

Airflow Range

 

 

 

 

 

CPC036***7B***

8

15

 

 

EHK7-10

15

20

10

1250-1350 CFM

EHK7-15

22

25

15

1400-1440 CFM

 

 

 

 

 

¹ Minimum Circuit Ampacity

 

 

 

 

² Maximum Overcurrent Protection device

kW Correction Factor

kW Correction Factor for 1- & 3-Phase Units

Supply Voltage

240

230

 

220

210

208

Correction Factor

1

0.93

 

0.82

0.78

0.76

 

 

 

 

 

 

 

Multiply rated kW by correction factor to get actual kW

 

 

 

 

 

 

 

kW Correction Factor for 480V Units

 

 

 

Actual Voltage

460

440

 

430

 

 

 

 

 

 

 

 

 

Correction Factor

0.92

0.84

 

0.8

 

 

 

 

 

 

 

 

 

For other voltage use voltage2 / 4802

 

 

 

 

 

 

 

 

 

kW Correction Factor for 575V Units

 

 

 

Supply Voltage

560

550

 

540

 

 

 

 

 

 

 

 

 

Correction Factor

0.95

0.91

 

0.88

 

 

 

 

 

 

 

 

 

Multiply rated kW by correction factor to get actual kW

Minimum Airflow for Electric Heat

Heater Size

Minimum CFM

 

 

A Models

B Models

 

 

 

 

10 kW

1,250

1,250

 

 

 

15 kW

1,400

1,250

 

 

 

SS-CPC36-72

www.goodmanmfg.com

7

Page 7
Image 7
Goodman Mfg SS-CPC36-72 dimensions Product Specifications, kW Correction Factor