Product Specifications
Heat Kit Electrical Data (Blower Only, Heat Mode) — 3 Tons
Model and | MCA¹ at | MOP² (amps) | Actual kW & | Recommended |
Heat Kit Usage | 208 / 240V | at 208 / 240V | BTU at 240V | Airflow Range |
CPC036***1D*** | 25 | 40 |
|
|
48 / 55 | 50 / 60 | 10 | ||
70 / 81 | 80 / 90 | 15 | ||
|
|
|
|
|
CPC036***3D*** | 17 | 25 |
|
|
29 / 33 | 30 / 35 | 10 | ||
42 / 48 | 45 / 50 | 15 | ||
|
|
|
|
|
CPC036***3B*** | 18 | 25 |
|
|
30 / 33 | 35 / 35 | 10 | ||
43 / 48 | 45 / 50 | 15 | ||
|
|
|
|
|
Model and | MCA¹ | MOP² (amps) | Actual kW & | Recommended |
Heat Kit Usage | at 480V | at 480V | BTU at 480V | Airflow Range |
|
|
|
|
|
CPC036***4B*** | 10 | 15 |
|
|
17 | 20 | 10 | ||
25 | 25 | 15 | ||
|
|
|
|
|
Model and | MCA¹ | MOP² (amps) | Actual kW & | Recommended |
Heat Kit Usage | at 575V | at 575V | BTU at 575V | Airflow Range |
|
|
|
|
|
CPC036***7B*** | 8 | 15 |
|
|
15 | 20 | 10 | ||
22 | 25 | 15 | ||
|
|
|
|
|
¹ Minimum Circuit Ampacity |
|
|
|
|
² Maximum Overcurrent Protection device
kW Correction Factor
kW Correction Factor for 1- &
Supply Voltage | 240 | 230 |
| 220 | 210 | 208 |
Correction Factor | 1 | 0.93 |
| 0.82 | 0.78 | 0.76 |
|
|
|
|
|
|
|
Multiply rated kW by correction factor to get actual kW |
|
|
| |||
|
|
|
| |||
kW Correction Factor for 480V Units |
|
|
| |||
Actual Voltage | 460 | 440 |
| 430 |
|
|
|
|
|
|
|
|
|
Correction Factor | 0.92 | 0.84 |
| 0.8 |
|
|
|
|
|
|
|
|
|
For other voltage use voltage2 / 4802 |
|
|
|
|
| |
|
|
|
| |||
kW Correction Factor for 575V Units |
|
|
| |||
Supply Voltage | 560 | 550 |
| 540 |
|
|
|
|
|
|
|
|
|
Correction Factor | 0.95 | 0.91 |
| 0.88 |
|
|
|
|
|
|
|
|
|
Multiply rated kW by correction factor to get actual kW
Minimum Airflow for Electric Heat
Heater Size | Minimum CFM | ||
|
| ||
A Models | B Models | ||
| |||
|
|
| |
10 kW | 1,250 | 1,250 | |
|
|
| |
15 kW | 1,400 | 1,250 | |
|
|
|