Goodman Mfg CPKF Split System Heat Pump manual Specifications, CPKF61-5, Capacities, Compressor

Models: CPKF Split System Heat Pump SS-ICPKF

1 12
Download 12 pages 62.4 Kb
Page 3
Image 3
Specifications

 

 

 

 

 

Product Specifications

Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPKF36-2*

CPKF36-5*

CPKF48-5*

CPKF60-5*

CPKF61-5*

 

 

 

 

 

 

 

Capacities

 

 

 

 

 

 

Nominal Cooling (BTU/h)

33,000

35,000

48,000

53,000

57,000

 

EER¹

9.0

9.0

9.0

9.0

9.0

 

Nominal Heating (BTU/h)

32,000

32,000

48,000

54,000

61,000

 

Decibels

78

78

78

80

80

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

RLA

15.9

5.7

8.2

9.0

10.9

 

LRA

104

42

64

74

101

 

Volts

220-240

380-415

380-415

380-415

380-415

 

 

 

 

 

 

 

 

Condenser Fan Motor

 

 

 

 

 

 

Horsepower

¼

FLA

0.9

1.2

1.2

1.2

1.2

 

Volts

220-240

380

380

380

380

 

 

 

 

 

 

 

 

Refrigeration System

 

 

 

 

 

 

Liquid Valve Size (“O.D.)

⅜"

⅜"

⅜"

⅜"

⅜"

Suction Valve Size (“O.D.)

¾"

¾"

⅞"

⅞"

⅞"

Valve Type

Sweat

Sweat

Sweat

Sweat

Sweat

Refrigerant Charge (oz.)

110

110

137

138

167

 

Shipped with Orifice Size (in.)

0.073

0.073

0.084

0.093

0.093

 

 

 

 

 

 

 

 

Condenser Fan / Coil

 

 

 

 

 

 

Horsepower - RPM

¼ - 950

⅓ - 1,075

⅓ - 1,075

⅓ - 1,075

⅓ - 1,075

Fan Diameter/ # Fan Blades

20/3

20/3

22/3

22/3

22/3

 

Outdoor Nominal CFM

1,800

1,800

2,600

2,600

3,200

 

Face Area (ft²)

14.58

14.58

17

17

17

 

Rows Deep/ Fins per Inch

1/19

1/19

1/19

1/22

1/22

 

Fin Type

Ripple

Ripple

Ripple

Ripple

Ripple

Coil No. of Tubes

24

24

24

36

36

 

Coil Tube Diameter (in.)

0.375

0.375

0.375

0.375

0.375

 

 

 

 

 

 

 

 

Electrical Data

 

 

 

 

 

 

Voltage-Hz / Phase

220/240-50/1

380/415-50/3

380/415-50/3

380/415-50/3

380/415-50/3

 

Min. Circuit Ampacity²

20.8

8.3

11.5

12.5

14.8

 

Max. Overcurrent Protection

35

15

15

20

25

 

(amps)³

 

 

 

 

 

 

 

Min / Max Volts

198/264

342/456

342/456

342/456

342/456

 

Power Supply Conduit Size

½ or ¾

½ or ¾

½ or ¾

½ or ¾

½ or ¾

 

 

 

 

 

 

 

Ship Weight (lbs-[kg])

206 [94]

206 [94]

216 [98]

248 [113]

249 [113]

 

 

 

 

 

 

 

 

¹ Energy Efficiency Ratio

²Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ³ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.

Note: Always check the S&R plate for electrical data on the unit being installed.