Product Specifications
GSC13 Commercial Product Specifications
GSC13
0363B*
GSC13
0483B*
GSC13
0484B*
GSC13
0603B*
GSC13
0604B*
Cooling Capacities
Nominal Cooling (BTU/h) | 40,792 | 48,000 | 45,500 | 60,000 | 55,500 |
|
|
|
|
|
|
SEER | 13 | 13 | 13 | 13 | 13 |
|
|
|
|
|
|
Decibels | 74 | 76 | 76 | 77 | 77 |
|
|
|
|
|
|
Compressor |
|
|
|
|
|
RLA / LRA
Type
9 / 65.5 | 12.4 / 88 | 5.8 / 44 | 14.7 / 91 | 7.1/50 |
Recip | Scroll | Scroll | Scroll | Scroll |
|
|
|
|
|
Condenser Fan Motor
Horsepower | 1/6 | 1/4 | 1/4 | 1/4 | 1/4 |
|
|
|
|
|
|
FLA | 1.1 | 1.5 | 0.8 | 1.5 | 0.8 |
|
|
|
|
|
|
Refrigeration System |
|
|
|
|
|
|
|
|
|
|
|
Liquid Valve Size (“O.D.) | ⅜" | ⅜" | ⅜" | ⅜" | ⅜" |
|
|
|
|
|
|
Suction Valve Size (“O.D.) | 1⅛" | 1⅛" | 1⅛" | 1⅛" | 1⅛" |
|
|
|
|
|
|
Refrigerant Charge | 83 | 140 | 102 | 167 | 131 |
|
|
|
|
|
|
Valve Type | Sweat | Sweat | Sweat | Sweat | Sweat |
|
|
|
|
|
|
Electrical Data |
|
|
|
|
|
|
|
|
|
| |
AC Volts/ Hz | 460/ 60 | 460/ 60 | |||
|
|
|
|
|
|
Min. Circuit Ampacity ¹ | 12.4 | 17 | 8.0 | 19.9 | 9.7 |
|
|
|
|
|
|
Max. Overcurrent Device ² | 20 | 20 | 15 | 30 | 15 |
|
|
|
|
|
|
Min / Max Volts | 197/253 | 197/253 | 414/506 | 197/253 | 414/506 |
|
|
|
|
|
|
Electrical Conduit Size | ½" or ¾" | ½" or ¾" | ½" or ¾" | ½" or ¾" | ½" or ¾" |
|
|
|
|
|
|
Ship Weight (lbs) | 182 | 189 | 207 | 196 | 242 |
|
|
|
|
|
|
¹Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes ² Must use
³ Installer will need to supply ¾” to ⅞” adapters for suction line connections.
4Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.
Notes
•Always check the S&R plate for electrical data on the unit being installed.
•Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
www.goodmanmfg.com | 3 |