Goodmans GSC13 warranty GSC10 Commercial Product Specifications

Models: GSC13

1 28
Download 28 pages 51.36 Kb
Page 4
Image 4
GSC10 Commercial Product Specifications

Product Specifications

GSC10 Commercial Product Specifications

GSC10

0903A*

GSC10

0904AC

GSC10

1203A*

GSC10

1203B*

GSC10

1204B*

Cooling Capacities

Nominal Cooling (BTU/h)

87,000

87,000

109,000

114,000

109,000

 

 

 

 

 

 

EER/IEER

11.2/11.5

11.2/11.5

11.2/---

11.2/11.2

11.2/11.2

 

 

 

 

 

 

Decibels

84

84

84

84

84

 

 

 

 

 

 

Compressor

 

 

 

 

 

RLA / LRA

Type

25.6 / 196

12.8 / 100

30.1 / 225

30.1 / 225

15.5/ 114

Scroll

Scroll

Scroll

Scroll

Scroll

 

 

 

 

 

Condenser Fan Motor

Horsepower

FLA

1

1

1

1

1

5.6

3.5

5.6

5.6

3.5

 

 

 

 

 

Refrigeration System

Liquid Valve Size (“O.D.)

⅝"

⅝"

⅝"

⅝"

⅝"

 

 

 

 

 

 

Suction Valve Size (“O.D.) (7½ tons)

1⅜"

1⅜"

1⅜"

1⅜"

1⅜"

 

 

 

 

 

 

Suction Valve Size (“O.D.) (10 tons)

1⅝"

1⅝"

1⅝"

1⅝"

1⅝"

 

 

 

 

 

 

Refrigerant Charge

35

35

35

35

35

 

 

 

 

 

 

Valve Type

Sweat

Sweat

Sweat

Sweat

Sweat

 

 

 

 

 

 

Electrical Data

 

 

 

 

 

 

 

 

 

 

AC Volts/ Hz

208-230/ 60

460/ 60

208-230/ 60

460/ 60

 

 

 

 

 

 

Min. Circuit Ampacity ¹

37.6

19.5

43.2

43.2

22.9

 

 

 

 

 

 

Max. Overcurrent Device ²

60

30

70

70

35

 

 

 

 

 

 

Min / Max Volts

197/253

414/ 506

197/253

197/253

414/ 506

 

 

 

 

 

 

Electrical Conduit Size

½" or ¾"

½" or ¾"

½" or ¾"

½" or ¾"

½" or ¾"

 

 

 

 

 

 

Ship Weight (lbs)

315

315

334

334

334

 

 

 

 

 

 

¹Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes ² Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.

³ Installer will need to supply ¾” to ⅞” adapters for suction line connections.

4Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.

Notes

Always check the S&R plate for electrical data on the unit being installed.

Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.

4

www.goodmanmfg.com

SS-GSCC

Page 4
Image 4
Goodmans GSC13 warranty GSC10 Commercial Product Specifications