Greenheck Fan 452413 manual Amerex Wiring Plan View, Canopy Hood

Models: 452413

1 40
Download 40 pages 18.74 Kb
Page 27
Image 27
Amerex Wiring Plan View
CURRENT DRAW MAX: 8A RESISTIVE
8A INDUCTIVE 120VAC

Amerex Wiring Plan View

POWER SOURCE

MANUAL RESET RELAY

 

PRM

ELECTRIC GAS VALVE

MICROSWITCH

INSTALLER PROVIDED JUNCTION BOXES

BASIC WIRING DIAGRAM

POWER SOURCE

MANUAL RESET RELAY

RED (COMMON)

YELLOW (N.O)

BLACK (N.C.)

GAS VALVE

NOTE: DO NOT USE YELLOW WIRE ON MICROSWITCH IN NORMAL

MICROSWITCHINSTALLATION. THE YELLOW WIRE IS TO BE USED ONLY FOR EXTINGUISHER ALARM, LIGHTS, CIRCUITS, ETC.

BASIC WIRING DIAGRAM

 

MANUAL RESET RELAY

 

RED (COMMON)

L1

 

120V/60HZ

 

 

 

 

L2

 

 

K1

 

 

Ka

PUSHBUTTON SWITCH

YELLOW (N.O)

K1b

 

 

 

 

BLACK (N.C.)

 

MICROSWITCH

NOTES:

1. DENOTES FIELD INSTALLATION

2.DENOTES FACTORY INSTALLATION

3.GAS VALVE: UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL OR LP GAS AS NEEDED OF APPROPRIATE PRESSURE AND TEMPERATURE RATING, 110V/60HZ OR AMEREX GAS VALVES, PN 12870, 12871, 12872, 12873, 12874, 12875 and 12876.

4.K1a and K1b ARE N.0. WHEN K1 IS DE-ENERGIZED.

GAS VALVE

SEE NOTE 3

Fig. 46