Start-Up of Coil Module
Hot Water, Chilled Water and DX Coils
1. Piping should be in accordance with accepted |
industry standards. Pipework should be supported |
independently of the coils. Water pipes are copper |
with sweat connections. USE WET TOWEL TO |
AVOID BURNING COIL CONNECTION GROMMETS. |
When installing coupling, do not apply undue |
stress to the connection extending through the |
unit. Use a |
the weld between coil connection and header. |
2. Connect the water supply to the bottom |
connection on the |
return to the top connection on the |
side. The extra bottom connection can be used for |
an auxiliary manual drain connection, and the extra |
top connection may be used for an automatic air |
vent or the extra connections can be capped. To |
ensure proper venting, an external air vent in the |
piping is recommended. Connecting the supply |
and/or return in any other manner will result in very |
poor performance. CAP UNUSED CONNECTIONS. |
3. The air vent at the uppermost point should be |
temporarily opened during system |
release all of the air from the coil. To maintain heat |
3.When connecting suction and liquid connections, make sure the coil is free from all foreign material. Make sure all joints are tight and free of leakage.
4.Dual circuits are recommended to be run by two compressors. One compressor with the appropriate valves and piping can be used but is not recommended. Greenheck does not supply compressor or condensing units, for further instruction on DX coil installation and operation contact your compressor and/or condenser manufacturer.
DXI coils have dual connections and should be used with two compressors.
WARNING
Standard unit insulation of 1.5 lbs. density has an insulation
For applications where the unit discharge temperatures are below 55°F. and the unit is installed in a warm, humid environment, additional insulation may need to be applied to the exterior of the unit to prevent condensation.
Steam Coils
Application Recommendations
transfer capacity, periodically vent any air in coil. |
Vent to to be located behind connections side |
access door. |
4. Water coils are not normally recommended for |
use with entering air temperatures below 40°F. |
No control system can be depended on to be |
100% safe against |
Glycol solutions or brines are the only safe media |
for operation of water coils with low entering air |
conditions. |
WARNING
Continuous water circulation through the coil at all times is highly recommended.
5. Pipe sizes for the system must be selected on the |
basis of the head (pressure) available from the |
circulation pump. Piping should be in accordance |
with accepted industry standards. |
Satisfactory operation and service life are best ensured when
coils are installed with proper piping,
trap and support arrangement. The following notes
and drawing are recommended for the coil unit installation and operation.
General
1. Provide separate supports and hangers for the unit and the piping.
Main
Steam
Return | Main |
|
|
|
|
|
|
| |
Strainer |
|
|
|
|
|
|
|
| |
Gate Valve |
|
|
| Float & Thermostat Trap |
|
|
| ||
|
|
| Check Valve | |
Control Valve |
|
|
| |
Modulating |
| Vacuum Breaker |
Steam Coil Piping
6. For chilled water coils, the condensate drain |
pipe should be sized adequately to ensure the |
condensate drains properly. See Drain Pan Traps |
section and related drawing. |
Direct Expansion (DX) Coils
1.Piping should be in accordance with accepted industry standards. Pipework should be supported independently of the coils. Undue stress should not be applied at the connection to coil headers.
2.The condensate drain pipe should be sized adequately to ensure the condensate drains properly. See Drain Pan Traps and related drawing.
2.Be certain that adequate piping flexibility is provided. Stresses resulting from expansion of closely coupled piping and coil arrangement can cause serious damage.
3.Standard steam coils are pitched in the casings when installed for horizontal airflow. The casing must be level after the unit is installed for proper condensate drainage. If condensate is not removed, the coil will suffer from water hammering and will have a shortened life. On vertical airflow applications, the coils must be pitched when installed.
®
Model VFCD/VFCB Vertical Fan Coil 11