Table of Contents
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Rigging/Placing Equipment. . . . . . . . . 4 Duct Connections. . . . . . . . . . . . . 5
Plumbing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Detergent Dispenser. . . . . . . . . . . . 5 Cabinet Assembly. . . . . . . . . . . . . 5
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Electrostatic Cell Wiring. . . . . . . . . . . 6 Exhaust Fan Motor Wiring. . . . . . . . . . 7 System Control Panel Wiring. . . . . . . . . 7
Initial System
Manual vs. Auto Operation. . . . . . . . . . 8
Operation.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Washing . . . . . . . . . . . . . . . . . . 9 Reset Mode . . . . . . . . . . . . . . . . 9
Detergent Dispenser . . . . . . . . . . . . 10 Adjustments. . . . . . . . . . . . . . . . 10 Flow Control Valve Adjustment. . . . . . . . 10
Maintenance | 10 |
Maintenance Log | 12 |
Warranty | 12 |
An aluminum mesh
NOTE
Power Play is designed to remove
System Components
NOTE
Grease Grabber™ Power Play System Function
Grease Grabber Power Play is an electrostatic precipitator style air filtration unit, with an additional carbon filter module, designed for two specific functions:
•Remove smoke/grease particles from kitchen exhaust.
•Remove odor molecules from kitchen exhaust.
NOTE
Grease Grabber Power Play must be connected to a listed exhaust hood assembly and must be installed in accordance with local building codes, NFPA 96 and NEC.
NOTE
The unit must be installed with a minimum 18 inch clearance to combustible materials and must be installed as part of a listed duct assembly.
The installation criteria for each of the system components shown below should be considered when selecting a site for install. For further detail on installing the components, refer to the INSTALLATION section on page 4.
Cabinet Assembly
The unit body is shipped on a common mounting rail ready for installation. If the unit was ordered with an exhaust fan, the fan will also be mounted as part of the cabinet assembly. Unless specified at time of order, the cabinet assembly must be mounted indoors and be protected from weather as well as be easily accessible for service personnel. (1) 1½ or 2 inch (depending on unit size) water supply line and (1)
3 inch waste water drain line is required at the unit for the system’s wash function.
Safety Filters & Carbon Panels
Filter and ionizer cell quantities for each stage are based on unit size (see table on page 4). A consistent quantity of filters/ionizer cells are provided for each stage of the unit
Grease Grabber™ Power Play Kitchen Exhaust Pollution Control System 3