Filter Quantities
Unit | Safety Filter | Safety Filter | |
Quantity | Quantity | ||
Size | |||
(2 ft. tall x 2 ft. wide) | (2 ft. tall x 1 ft. wide) | ||
| |||
|
|
| |
1 | 1 | ||
|
|
| |
2 | 0 | ||
|
|
| |
2 | 1 | ||
|
|
| |
3 | 0 | ||
2 | 2 | ||
4 | 0 | ||
4 | 2 | ||
6 | 0 | ||
|
|
| |
6 | 2 | ||
|
|
| |
8 | 0 | ||
|
|
| |
8 | 2 | ||
|
|
| |
3 | 3 | ||
6 | 0 | ||
6 | 3 | ||
9 | 0 | ||
9 | 3 | ||
|
|
| |
12 | 0 | ||
|
|
| |
12 | 3 | ||
|
|
|
Remote Mounted Detergent Dispenser
A 55 gallon remote mounted detergent dispenser is included as part of the electrostatic collector
Remote Mounted System Control Panel and Power Pack (2 pieces)
The system control panel allows the user to interface with the unit and controls operation as well as monitors wash and other functions. The Power Pack contains a power transformer and works in conjunction with the System Control Panel and the unit’s high voltage ionizer cells. The System Control Panel should be mounted in an area easily accessible to daily operational staff. The Power Pack should be mounted as close as possible to the System Control Panel and both should be mounted as close to the cabinet assembly as possible. Allow adequate room from the face of the panels for door swing clearance and servicing.
High Voltage Cable
High voltage cable is supplied to connect the ionizer/ collector sections of the precipitator to the ionizer and collector terminals in the Power Pack. The red cable (50 ft supplied) is used for the ionizer and the blue cable (50 ft supplied) is used for the collector. Refer to the ELECTRICAL section for details on wiring.
Installation
Rigging/Placing Equipment
1.The unit is furnished with lifting lugs at the four corners and along the length as necessary.
2.Lift into place using all the lifting lugs.
3.Field weight will vary depending upon final selections such as fan type, accessories, etc. Approximate weights are shown in the table below.
Unit Size | Approximate | Approximate | |
Weight (lbs) | Weight (kg) | ||
| |||
|
|
| |
3100 | 1409 | ||
|
|
| |
3620 | 1645 | ||
|
|
| |
4025 | 1830 | ||
|
|
| |
4280 | 1945 | ||
4000 | 1818 | ||
4580 | 2082 | ||
5200 | 2364 | ||
5700 | 2591 | ||
|
|
| |
6420 | 2918 | ||
|
|
| |
7080 | 3218 | ||
|
|
| |
7560 | 3436 | ||
|
|
| |
5200 | 2364 | ||
6140 | 2791 | ||
6800 | 3091 | ||
7325 | 3330 | ||
8275 | 3761 | ||
|
|
| |
8800 | 4000 | ||
|
|
| |
9510 | 4350 | ||
|
|
|
4.The unit can be positioned on a base or curb suitable for this purpose.
5.The unit must be anchored to its base/curb.
6.Alternatively, the unit may be suspended from an adequate overhead structure, using suitable undercarriage or hanging rods (by others). If the unit is suspended by hanging rods, minimum 1/2 inch (12.7 mm) diameter threaded rod is to be used. All hanger brackets/lifting lugs must be used to ensure proper support of the unit. The unit must also be hung level to ensure proper operation.
7.A service clearance of 42 inches must be provided on the access door side of the unit.
8.A minimum 18 inch clearance must be maintained between this unit and any combustible material.
4Grease Grabber™ Power Play Kitchen Exhaust Pollution Control System