Roof Downblast - Exhaust Direct Drive
G-060 • G-065
193⁄8
(492)
17
(432)
*121⁄8
(308)
3(76)
13⁄4 (44)
Static Pressure (Pa)
| RPM (Direct) |
Density | 0.075 lb/ft3 |
Density 1.2 kg/m3 | |
StaticPressure(in.wg) |
|
Damper Size = 8 x 8 (203 x 203)
Roof Opening = 101/2 x 101/2 (267 x 267) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 15 lbs. (7 kg)
All dimensions in inches (millimeters).. *May be greater depending on motor..
^Weight shown is largest cataloged Open
Volume (cfm)
Volume (m3/hr )
Direct Drive RPM
Motor | Fan |
|
|
|
| Static Pressure in Inches wg |
|
|
|
| |||
HP | RPM |
| 0 | 0..05 | 0..1 | 0..125 | 0..15 | 0..2 |
| 0..25 | 0..3 | 0..375 | 0..4 |
060 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CFM | 138 | 116 | 90 | 73 | 53 |
|
|
|
|
|
|
1050 | BHP | 0..00 | 0..00 | 0..01 | 0..01 | 0..01 |
|
|
|
|
|
| |
|
| Sones | 1..7 | 1..7 | 1..7 | 1..7 | 1..7 |
|
|
|
|
|
|
|
| CFM | 170 | 153 | 135 | 125 | 113 | 85 |
|
|
|
|
|
1300 | BHP | 0..01 | 0..01 | 0..01 | 0..01 | 0..01 | 0..01 |
|
|
|
|
| |
|
| Sones | 2..9 | 2..8 | 2..8 | 2..7 | 2..7 | 2..6 |
|
|
|
|
|
|
| CFM | 203 | 188 | 173 | 166 | 158 | 140 |
| 120 | 92 |
|
|
1550 | BHP | 0..01 | 0..01 | 0..01 | 0..01 | 0..02 | 0..02 |
| 0..02 | 0..2 |
|
| |
|
| Sones | 4..2 | 3..9 | 3..8 | 3..8 | 3..8 | 3..7 |
| 3..7 | 3..6 |
|
|
065 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CFM | 187 | 161 | 130 | 110 | 87 |
|
|
|
|
|
|
1050 | BHP | 0..01 | 0..01 | 0..01 | 0..01 | 0..01 |
|
|
|
|
|
| |
|
| Sones | 2..2 | 2..1 | 1..9 | 1..8 | 1..7 |
|
|
|
|
|
|
|
| CFM | 231 | 211 | 189 | 178 | 163 | 130 |
| 92 |
|
|
|
1300 | BHP | 0..01 | 0..01 | 0..01 | 0..01 | 0..01 | 0..01 |
| 0..01 |
|
|
| |
|
| Sones | 3..2 | 3..1 | 3..0 | 2..9 | 2..9 | 2..8 |
| 2..7 |
|
|
|
|
| CFM | 276 | 259 | 241 | 232 | 223 | 201 |
| 176 | 145 | 96 |
|
1550 | BHP | 0..02 | 0..02 | 0..02 | 0..02 | 0..02 | 0..02 |
| 0..02 | 0..02 | 0..02 |
| |
|
| Sones | 4..9 | 4..6 | 4..5 | 4..5 | 4..4 | 4..3 |
| 4..3 | 4..1 | 4..0 |
|
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels.
14