Greenheck Fan LFC manual Drain Pan / Drain Trap, Steam Coils, General

Models: LFC

1 16
Download 16 pages 12.59 Kb
Page 10
Image 10

Steam Coils, General - continued

3.Standard steam coils are pitched in the casings when installed for horizontal airflow. The casing must be level after the unit is installed for proper condensate drainage. If condensate is not removed, the coil will suffer from water hammering and will have a shortened life. On vertical airflow applications, the coils must be pitched when installed.

4.Do not reduce pipe size at the coil return connection. Carry return connection size through the dirt pocket, making the reduction at the branch leading to the trap.

5.It is recommended that vacuum breakers be installed on all applications to prevent retaining condensate in the coil. Generally, the vacuum breaker is to be connected between the coil inlet and the return main. The vacuum breaker should be open to the atmosphere and the trap design should allow venting of large quantities of air.

6.Do not attempt to lift condensate when using modulating or on-off control.

7.Do not reduce the pipe size leaving the coil.

Traps

1.Size traps in accordance with the manufacturer’s recommendations. Be certain that the required pressure differential will always be available. DO NOT UNDERSIZE.

2.Float and thermostatic or bucket traps are recommended for low pressure steam. On high pressure systems, bucket traps are normally recommended. The thermostatic traps should be used only for air venting.

3.Bucket traps are recommended for use with on-off control only.

4.Locate traps at least 12 inches below the coil return connection.

Controls

1.On high pressure installations, a two-position steam valve with a face and bypass arrangement is preferred where modulating control is required.

2.Modulating valves must be sized properly. DO NOT UNDERSIZE.

Freezing Conditions (entering air below 35°F)

1.5 PSI steam must be supplied to the coil at all times.

2.Modulating valves are not recommended. Control should be by means of face and bypass dampers.

3.Provision should always be made to thoroughly mix fresh air and return air before it enters the coil on return air units. Also, temperature control elements must be properly located to obtain true air mixture temperatures.

4.As additional protection against freeze-up, the trap should be installed sufficiently—­far below the coil to provide an adequate hydrostatic head to ensure removal of condensate during an interruption in the steam pressure. Estimate 3 feet for each 1 PSI of trap differential required.

5.On start-up, admit steam to coil ten minutes before admitting outdoor air.

6.Provision must be made to close fresh air dampers if steam supply pressure falls below minimum specified.

Drain Pan / Drain Trap

Drain lines and traps should be run full size from the drain pan connection. Drain pans should have drain lines and traps to permit the condensate from the coils to drain freely. On all units with drain pans, the trap depth and the distance between the trap outlet and the drain pan outlet should be twice the static pressure (P) in the drain pan section under normal operation to assure the trap remains sealed.

2P = minimum

2P = minimum

Drain Pan / Drain Trap

10 Model LFC Low-Profile Fan Coil

®

Page 10
Image 10
Greenheck Fan LFC manual Drain Pan / Drain Trap, Steam Coils, General

LFC specifications

Greenheck Fan LFC is a prominent player in the realm of ventilation and air movement solutions, known for its innovative approach to fan technology. The LFC series offers a range of features specifically designed to enhance indoor air quality while maintaining energy efficiency. One of the standout aspects of the LFC series is its application in both commercial and industrial settings, providing versatile solutions for various ventilation requirements.

One of the main features of the Greenheck Fan LFC is its direct drive design. This configuration eliminates the need for belts and pulleys, reducing maintenance requirements and increasing reliability. The direct drive system also allows for quieter operation, making it ideal for environments where noise control is critical, such as schools and healthcare facilities. With a wide range of motor options available, users can select the most appropriate solution for their specific airflow and energy consumption needs.

The LFC series is engineered with high-efficiency impellers, which greatly enhance airflow performance while minimizing energy usage. These impellers are designed to optimize air movement, allowing the fans to operate more efficiently across different speed settings. This focus on efficiency is not only beneficial for reducing operational costs but also contributes to sustainability efforts by lowering energy consumption, which is increasingly important in today’s environmentally conscious market.

Moreover, the LFC series features advanced aerodynamic designs that help to streamline airflow, reducing turbulence and improving overall system efficiency. This design innovation leads to better performance in applications requiring precise ventilation control. The fans can be equipped with variable frequency drives (VFDs), enabling dynamic control over fan speed and further enhancing energy efficiency by adapting airflow to real-time demands.

Durability is another hallmark of the Greenheck Fan LFC. Constructed from high-quality materials that resist corrosion and wear, these fans are built to withstand the rigors of harsh environments, ensuring long service life. Additionally, the LFC series can be customized with various coatings and finishes, making them suitable for diverse industrial applications.

In summary, the Greenheck Fan LFC series combines advanced technology with user-centric design. Its key features—such as direct drive systems, high-efficiency impellers, advanced aerodynamics, and robust construction—position it as a leading choice for effective and efficient ventilation solutions. Whether employed in commercial spaces or heavy-duty industrial applications, the LFC fans represent a commitment to quality and performance in air movement technology.