Greenheck Fan OFD-XXX Series, OFSD-XXX Series Damper Is Installed Outside Of Wall Plane, Ofsd-Xxx

Models: OSSFD-XXX Series OFD-XXX ODFD-XXX Series OFD-XXX Series ODFD-XXX OFSD-XXX OFSD-XXX Series

1 6
Download 6 pages 34.81 Kb
Page 3
Image 3
1. DAMPER IS INSTALLED OUTSIDE OF WALL PLANE

1. DAMPER IS INSTALLED OUTSIDE OF WALL PLANE

OFSD-XXX

Figure 1 shows two approved installations for

combination fire smoke dampers: 1) “Through the

grille access” and 2) installation in continuing duct.

To provide "through the grille" access to the damper

actuator, the damper is located toward the back of the

sleeve and the actuator is installed between the damper

and grille. Actuator and damper can be accessed and

serviced by removing the grille. To provide access to the

damper actuator for continuing ductwork, refer to the

requirements of NFPA 90A.

ODFD-XXX, OFD-XXX, and OSSFD-XXX: Figure

1 shows two installations that are also approved for

curtain fire dampers. For access to inspect the damper

and fusible link, refer to the requirements of NFPA 90A.

2. CLEARANCE REQUIREMENTS

There is no minimum clearance requirement between

the wall/floor opening and the sleeve exterior (with

thermal blanket attached). However, to facilitate

installation, clearances between the wall/floor opening

and the damper sleeve are recommended. although

there is no maximum allowable clearance, the minimum

overlap requirements between the wall/floor and the

flange/retaining angle must be met. On grill mount

installations the flange must overlap the wall/floor by

1⁄2 in. (13mm). On continuous duct installations, the

retaining angles must overlap the wall/floor by 1 in.

(25mm). Because no clearances are required betweeen

the wall/floor opening and the sleeve, dampers may not

be installed in the plane of the wall using this installation

method.

3. DUCT TO SLEEVE CONNECTIONS

Steel stud

 

 

 

 

 

#10 sheet metal screws

 

 

 

 

 

spaced 6 in. on center and

 

5/8 in . x 1 in. 16 ga.

 

 

 

maximum of 2 in. from the

 

 

 

 

corners (minimum of 2

 

angles minimum

 

 

 

 

 

 

 

screws per side). Screw into

 

(Refer to Section 4)

 

 

 

 

 

 

 

rear portion of the studs so

 

 

 

 

 

 

 

 

 

 

as to avoid space conflicts

 

 

 

 

 

with the grille assembly.

 

 

Factory Supplied

 

 

Thermal Blanket

 

 

 

 

 

Factory Supplied

 

 

 

 

 

Grille

 

 

 

 

Thermal Blanket

 

 

 

 

 

(Supplied

 

 

 

 

 

by others)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fire damper or

Fire damper or

7 1/2 in.

combination fire

combination fire

smoke damper

Max.

smoke damper

 

“Duct Terminates” Metal Stud

Note: Both installations may be vertical or horizontal.

Gypsum Wallboard

Dampers are supplied with actuators (on applicable

models) and sleeves from the factory and can be

installed without the need for additional field installed

sleeves.

Sleeve gauges of 20-14 (.9mm - 2mm) are to be used.

UL Standard 555 requires all ducts to terminate at fire

damper sleeves. Sleeve thickness must not be less than

the gauge of the connecting duct.

Duct to sleeve breakaway connections must be of the

type described on page 5. Factory furnished round duct

collars on type R and CR dampers are also considered

to be breakaway connections and may be used.

Wooden Stud Construction

Stud or Runner

In wood stud construction, gypsum wallboard must cover all wood stud surfaces.

1in. x 1 in. 16 ga. angle minimum (Refer to section 4)

Factory Supplied Thermal Blanket

 

Grille

Factory Supplied

(Supplied

by others)

Thermal Blanket

 

7 1/2 in.

Max.

6 1/2 in.

Fire damper or

combination fire

Max.

smoke damper

 

“Duct Terminates” Wood Stud

re

Fire damper or

combination fire

r

smoke damper

 

“Duct Continues”

Figure 1: Installation configurations for ‘Out of Wall’ curtain fire dampers and combination fire smoke dampers. 3

Page 3
Image 3
Greenheck Fan OFD-XXX Series Damper Is Installed Outside Of Wall Plane, Ofsd-Xxx, ODFD-XXX, OFD-XXX,and OSSFD-XXX Figure