Greenheck Fan ODFD-XXX Series, OFSD-XXX Series Actuator Connections, Sleeved damper with Thermal

Models: OSSFD-XXX Series OFD-XXX ODFD-XXX Series OFD-XXX Series ODFD-XXX OFSD-XXX OFSD-XXX Series

1 6
Download 6 pages 34.81 Kb
Page 4
Image 4
5. ACTUATOR CONNECTIONS

4.SECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL OPENINGS.

Damper/sleeve assemblies must be installed in wall openings using flanges and sheet metal screws as illustrated and described below.

Flange on front (grille end) of sleeve must be a minimum of 16 gauge (1.5mm) steel and have a 58 in. (16mm) minimum flange leg (refer to Figure 2). Using #10 (19mm) sheet metal screws, screw from inside of sleeve through the rear portion of the studs (as shown in Figure 1). Space screws a maximum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from the corners (minimum of 2 screws per side).

No retaining angles are required on the side of wall opposite from the grille.

Retaining angles on continuing duct must be a minimum of 112 in. x 112 in. (38mm x 38mm) 16 gauge (1.5mm) steel (refer to Figure 3). Screwing sleeve to steel studs is not required.

Retaining angles must be attached to the sleeve using one or more of the following methods of attachment:

Tack or spot welds

#10 (19mm) sheet metal screws

14 in. (6mm) bolts and nuts

316 in. (4.7mm) steel pop rivets

Attachments must be spaced a minimum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from corners. The angles must be attached to all 4 sides of the sleeve. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners.

caution! Do not tear the thermal blanket during installation.

Dampers are tested for correct operation and are square and straight before shipment from the factory. Dampers must be installed square and straight and must not be twisted or racked. Failure to install the damper square and straight may prevent the damper blades from operating open and closed.

5. ACTUATOR CONNECTIONS

Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and piping diagrams developed in

'MBOHF

5IFSNBM#MBOLFU

JOTUBMMFEBSPVOEFOUJSF

PVUTJEFTVSGBDFPGTMFFWF

8BMM

Figure 2: Sleeved damper with Thermal

Blanket (duct termination).

3FUBJOJOH"OHMF

5IFSNBM#MBOLFU

JOTUBMMFEBSPVOE

FOUJSFPVUTJEF

TVSGBDFPGTMFFWF

JO

.

BY

JO

.

BY

JO

.

BY

JO

.

BY

8BMM

Figure 3: Sleeved damper with Thermal

Blanket (duct continuation).

Note: Thermal blanket is riveted to the damper sleeve and the seam is taped with acrylic adhesive tape, FSK facing tape 152 5CWnt, manufacuted by Venture Tape Company.

compliance with applicable codes, ordinances and regulations (see Electrical Guidelines).

6 Recommended Preparation of Openings in Wood and Metal Stud Walls

Frame wall openings as shown (see Figure 4)

Double vertical studs are not required for openings 36 in. x 36 in. (914mm x 914mm) or smaller.

Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening(see Figure 4).

All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance Directory) and/or local codes.

JO

JOPD

.BYJNVN

JOPD

JOPD

$FJMJOH3VOOFS

.BYJNVN

.BYJNVN

 

NFUBMTUVET

NFUBMTUVET

 

 

1BOIFBE

JO NN

 

 

 

4DSFXT

JO NN

 

 

JOPD

JOPD

 

.BYJNVN

.BYJNVN

 

XPPETUVET

XPPETUVET

 

4

'MPPS3VOOFS

Figure 4

Page 4
Image 4
Greenheck Fan ODFD-XXX Series, OFSD-XXX Series Actuator Connections, Sleeved damper with Thermal, Blanket duct termination