COMMERCIAL 100 kW

COMMERCIAL SERIES

OPERATING DATA

 

 

 

COMMERCIAL 100 kW

 

KW RATING

 

 

100

 

 

 

 

 

 

ENGINE SIZE

 

 

6.8 Liter V-10

 

 

 

 

 

 

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

 

KW

AMP

CB Size

120/240V, single phase, 1.0 pf

 

100 LP / 98 NG

416.6 LP / 408.3 NG

450

120/208V, 3-phase, 0.8 pf

 

100 LP / 98 NG

347.4 LP / 340.4 NG

400

120/240V, 3-phase, 0.8 pf

 

100 LP / 98 NG

301 LP / 295 NG

350

277/480V, 3-phase, 0.8 pf

 

100 LP / 98 NG

150.5 LP / 147.5 NG

175

 

 

 

 

 

GENERATOR LOCKED ROTOR KVA

 

 

 

 

AVAILABLE @ VOLTAGE DIP OF 35%

 

 

 

 

Single phase or 208V & 240V 3-phase

 

 

190

 

480V 3-phase

 

 

225

 

 

 

 

 

 

ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)

 

Natural Gas

 

Propane

 

 

(ft3/hr.)

(gal/hr.)

cu ft/hr

Exercise cycle

 

130

1.42

52.3

25% of rated load

 

371

4.06

149.4

50% of rated load

 

713

7.81

287.4

75% of rated load

 

994

10.88

400.4

100% of rated load

 

1260

13.80

507.8

 

 

 

 

 

ENGINE COOLING

ft3/min

 

 

 

Air flow (inlet air including alternator and combustion air)

 

5,500

 

System coolant capacity

US gal.

 

4.5

 

Heat rejection to coolant

BTU/hr.

 

342,000

 

Max. operating air temp. on radiator

°C (°F)

 

60 (150)

 

Max. ambient temperature

°C (°F)

 

50 (140)

 

 

 

 

 

 

COMBUSTION AIR REQUIREMENTS

 

 

 

 

Flow at rated power 60 Hz

cfm

 

262

 

 

 

 

 

 

SOUND EMISSIONS IN DBA

 

 

 

 

db(A) @ 23 feet in exercise mode

 

 

61

 

db(A) @ 23 feet at normal operating load

 

 

72

 

 

 

 

 

 

EXHAUST

 

 

 

 

Exhaust flow at rated output 60 Hz

cfm

 

888

 

Exhaust temp. at muffler outlet

°F

 

960

 

 

 

 

 

 

ENGINE PARAMETERS

 

 

 

 

Rated synchronous RPM

60 Hz

 

2300

 

HP at rated KW

60 Hz

 

168

 

 

 

 

 

 

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

 

 

 

 

Temperature Deration

 

 

 

 

3% for every 10 °C above - °C

 

25

 

1.65% for every 10 °F above - °F

 

77

 

Altitude Deration

 

 

 

 

1% for every 100 m above - m

 

183

 

3% for every 1000 ft. above - ft.

 

600

 

 

 

 

 

 

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.

Page 3
Image 3
Guardian Technologies QT10068 KW Rating, Engine Size, Generator Locked Rotor KVA Available @ Voltage DIP of 35%, Exhaust