4. Installation of water drainage pipe

(1) Install water drainage pipe

Pipe diameter shall be equal or larger than that of connecting pipe (Pipe of polythene; size: 25mm; O.D.: 32mm )

Drainpipe should be short, with a downward slope at least 1/100 to prevent air bag from forming.

If downward slope of drainpipe cannot be made,lifting pipe shall be installed. Keep a distance of 1-1.5m between suspending bolts, to make water hose straight.

1-1.5m

slope over 1/100

Use the drainage hose and clip provided with unit.

Insert water pipe into water plug until it reaches the white tape.

Tighten the clip until head of the screw is less than 4mm from hose.

Wind the ddrainage hose to the clip using seal pad for heat insulation.

Insulate drainage hose in the room.

 

Large size seal pad

Clip

(accessory)

 

Clip

 

 

 

 

 

 

 

 

 

Tape(white)

 

 

 

 

 

 

 

 

 

 

 

 

Draingage hose

Less than 4mm

5. Cautions for the water drainage lifting pipe

Installation height of water drainage lifting pipe shall be less than 280mm

There should be a right angle with unit ,300mm from unit.

Less than 300mm

1-1.5m Suspending bracket

Drainage hose

Drainage hose

 

 

Less than 280mm

 

220mm

220

500mmthan

 

Clip

 

Water drainage

 

 

 

lifting pipe

 

 

 

< Note >

 

 

Less

 

 

 

 

 

Less than 75mm

Less than 500mm

The slope of water drainage hose shall be within 75mm , make the drainage plug not to bear excessive force.

If several water hoses join together, of as per following procedures.

100mm ¸over

Slope less than 1/100

Connection drainage hose with a T-joint

 

Specifications of the selected drainage hoses shall meet the requirements for the unit running