Installation Procedures

7. Piping Connection

AB092XCERA

AB122XCERA

Flare connection

Gas pipe

3-way valve

 

 

Indoor

 

Outdoor

Unit

 

unit

 

Liquid

2-way valve

 

pipe

 

 

Flare connection

AB142XCERA

AB182XCERA

Flare connection

Gas pipe

3-way valve

 

A

 

 

Indoor

 

Outdoor

Unit

 

unit

 

Liquid

2-way valve

 

pipe

 

 

Flare connection

A(adaptor, from 9.52 to 12.7)

To gas pipe

To outdoor unit

(1) Dimension of connecting pipe

AB092XCERA

AB122XCERA

AB142XCERA

AB182XCERA

Gas pipe Liquid pipe Gas pipe Liquid pipe

9.52mm

6.35mm

12.7mm

6.35mm

Fit the nut on and fasten

(2) The maximum length and drop height of connecting pipe

The maximum length is 20m

The maximum drop height is 10m.

To ensure the efficiency , Pipes shall be as short as possible.

Cautions for piping connection

Do not twist or deform the connecting pipe.

Do not mix dusts.

The bending radius shall be as large as possible.

Both gas pipe and liquid pipe shall be heat insulation. No leakage in the flare.

(3) Piping connection Connecting method

Smear refrigerant oil on the joints of piping and flare. The bending radius shall be as large as possible. Align the pipe center when fastening, and tighten the nut, as shown in the figure.

Pay attention to not mix foreign matters such as sands in.

90 0.5O

Joint

Spanner

Spanner

Nut

 

Diameter of Pipe

Tighten Torque

(N.m)

 

Liquid Pipe 6.35mm

11.8

 

 

Gas Pipe 9.52mm

40

 

 

Gas Pipe 12.7mm

49.0

 

 

If not aligned ,tighten the nut by force will damage the nut that result in gas leakage

16