Failure code
The remote receiver can indicate the failure code
For | Failure | For | Failure description | Reason |
remote | code on | central |
|
|
type, | wired | control, |
|
|
flash | control | failure |
|
|
times | ler | code |
|
|
10 | 08 | 21 | Drainage system failure | Float switch broken down for more than |
|
|
|
| 25m continuously |
1 | 01 | 01 | Indoor ambient temp. sensor | Sensor broken down or short circuit for |
|
|
| failure | more than 2m continuously |
2 | 02 | 02 | Indoor coil temp. sensor failure | Sensor broken down or short circuit for |
|
|
|
| more than 2m continuously |
3 | 4A | 11 | Outdoor ambient temp. sensor | Sensor broken down or short circuit for |
|
|
| failure | more than 2m continuously |
4 | 49 | 12 | Outdoor coil temp. sensor A | Sensor broken down or short circuit for |
|
|
| failure(compressor discharging | more than 2m continuously |
|
|
| temp. sensor) |
|
5 | 48 | 10 | CT check abnormal 3 times in 30m | |
6 | 53 | 14 | High pressure abnormal | High pressure switch acts 3 times in 30m |
7 | 47 | 22 | Power failure in overvoltage or |
|
|
|
| lackvoltage, phase error (fixed |
|
|
|
| frequency multi split) |
|
8 | 07 | 06 | Communication between wired | Communication abnormal for more than |
|
|
| controller and indoor abnormal | 4m continuously |
9 | 06 | 05 | Communication between indoor | Communication abnormal for more than |
|
|
| and outdoor abnormal | 4m continuously |
11 | 0B | 30 | Outside alarm signal input | Outside signal broken down for more than |
|
|
|
| 10s |
14 | 4C | 15 | Fault in discharging temp. | Sensor broken down or short circuit for |
|
|
| sensor A | more than 2m continuously |
15 | 05 | 17 | EEPROM abnormal | EEPROM data missing |
16 | 54 | 26 | Outdoor pressure switch or | Pressure switch or discharging protector |
|
|
| discharging protector abnormal | disconnected; or CN11 on indoor PCB |
|
|
|
| disconnected. The failure occurs only when |
|
|
|
| there is no outdoor PCB. |
17 | 50 | 15 | Compressor overheat | Detected temperature of discharge line is |
|
|
|
| higher than 120* |
18 | 0C | 23 | Fault in operation mode (fixed | Indoor units operate in different modes |
|
|
| frequency multi split) |
|
19 | 4B | 18 | Outdoor coil temp. sensor B | Sensor broken down or short circuit for |
|
|
| failure | more than 2m continuously |
20 | 4D | 15 | Fault in discharging temp. | Detected temperature of discharge line is |
|
|
| sensor B | higher than 120* |
21 | 32D | 07 | Module failure | Module overheat, overcurrent, |
22 | 54D | 08 | Fault in | Current sensor failure or compressor is not |
|
|
|
| started |