Haier AB212XCEAA operation manual Failure code, The remote receiver can indicate the failure code

Models: AB212XCEAA

1 28
Download 28 pages 37.9 Kb
Page 27
Image 27
 Failure code

The remote receiver can indicate the failure code Failure code

The remote receiver can indicate the failure code

For

Failure

For

Failure description

Reason

remote

code on

central

 

 

type,

wired

control,

 

 

flash

control

failure

 

 

times

ler

code

 

 

10

08

21

Drainage system failure

Float switch broken down for more than

 

 

 

 

25m continuously

1

01

01

Indoor ambient temp. sensor

Sensor broken down or short circuit for

 

 

 

failure

more than 2m continuously

2

02

02

Indoor coil temp. sensor failure

Sensor broken down or short circuit for

 

 

 

 

more than 2m continuously

3

4A

11

Outdoor ambient temp. sensor

Sensor broken down or short circuit for

 

 

 

failure

more than 2m continuously

4

49

12

Outdoor coil temp. sensor A

Sensor broken down or short circuit for

 

 

 

failure(compressor discharging

more than 2m continuously

 

 

 

temp. sensor)

 

5

48

10

Over-current protection

CT check abnormal 3 times in 30m

6

53

14

High pressure abnormal

High pressure switch acts 3 times in 30m

7

47

22

Power failure in overvoltage or

 

 

 

 

lackvoltage, phase error (fixed

 

 

 

 

frequency multi split)

 

8

07

06

Communication between wired

Communication abnormal for more than

 

 

 

controller and indoor abnormal

4m continuously

9

06

05

Communication between indoor

Communication abnormal for more than

 

 

 

and outdoor abnormal

4m continuously

11

0B

30

Outside alarm signal input

Outside signal broken down for more than

 

 

 

 

10s

14

4C

15

Fault in discharging temp.

Sensor broken down or short circuit for

 

 

 

sensor A

more than 2m continuously

15

05

17

EEPROM abnormal

EEPROM data missing

16

54

26

Outdoor pressure switch or

Pressure switch or discharging protector

 

 

 

discharging protector abnormal

disconnected; or CN11 on indoor PCB

 

 

 

 

disconnected. The failure occurs only when

 

 

 

 

there is no outdoor PCB.

17

50

15

Compressor overheat

Detected temperature of discharge line is

 

 

 

 

higher than 120*

18

0C

23

Fault in operation mode (fixed

Indoor units operate in different modes

 

 

 

frequency multi split)

 

19

4B

18

Outdoor coil temp. sensor B

Sensor broken down or short circuit for

 

 

 

failure

more than 2m continuously

20

4D

15

Fault in discharging temp.

Detected temperature of discharge line is

 

 

 

sensor B

higher than 120*

21

32D

07

Module failure

Module overheat, overcurrent, short-circuit

22

54D

08

Fault in zero-load

Current sensor failure or compressor is not

 

 

 

 

started

25

Page 27
Image 27
Haier AB212XCEAA operation manual Failure code, The remote receiver can indicate the failure code