Haier AB212XCEAA Installation Procedure, Installation Of Indoor Unit, In the case of new ceiling

Models: AB212XCEAA

1 28
Download 28 pages 37.9 Kb
Page 19
Image 19
4. INSTALLATION OF INDOOR UNIT

In the case of new ceiling Installation Procedure

4. INSTALLATION OF INDOOR UNIT

In the case of new ceiling

(1) Install unit temporally

< After installation on the ceiling > Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.

(2)In the case of ceiling already exists As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details.

Manual background Center of the hole is marked on the paper pattern.

Center of the unit is marked on the card in the unit and on the paper pattern.

Manual background Mount paper pattern 5 onto unit using 3 screws 6 . Fix the corner of the drain pan at piping outlet.

< After installation on the ceiling >

(3)Adjust unit to its right position. (Refer to preparation for the installation-(1))

(4)Check unit's horizontal level.

Manual background Watert pump and flating switch is installed inside indoor unit, check four corners of the unit for its level using horizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage,

problem may occur on floating switch, causing water leakage.)

(5)Remove the washer mounlting 2 , and tighten the nut above.

(6)Remove the paper pattern.

In the case of ceiling already exists

(1)Install unit temporally

Manual background Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket. Fix the bracket firmly.

(2)Adjust the height and position of the unit.

(Refer to preparation for the installation (1) ).

(3) Proceed with 3 and 4 of "In the case of new ceiling".

Nut (Prepare in feild)

Washer (Prepared in feild)

Suspending bolts

Fasten (double nuts)

Level

Insert

Washer fixing pad (prepared in feild)

[ secure the washer firmly]

Polythene pipe

Screws at the piping outlet is fixed at the corner of drain pan.

Center of ceiling hole Paper pattern

Paper pattern 5

 

Screw (accessory)

Screw (accessory)

[Fix the paper pattern]

17

Page 19
Image 19
Haier AB212XCEAA operation manual Installation Procedure, Installation Of Indoor Unit, In the case of new ceiling