Installation Precedure
Outdoor Unit
1.Selecting the installation place Warning
It should be installed at places where it is firm enough to withstand the weight of the air conditioner to prevent falling. Typhoon and earthquake prevention. It should be installed according to specific requirements. Inappropriate installation may lead to accidents.
Dimension of outdoor unit
140
1000 |
660 |
750 |
660 |
1550 795
Installtion space
(1)During installation, connect the outdoor unit and align the mounting surface (See the figure on the right). Mount the electric distribution device on the external side of the unit in accordance to the installation instructions for electric distribution device.
| Blow out |
Absorb in | Absorb in |
| |
Absorb in |
|
| Working, repair surface |
(2)To ensure good performance of the machine and facilitate installation and maintenance, adequate space must be reserved (See figure on the right).
Note:
Obstacles should be 2000mm off the top of the outdoor unit. Obstacles nearby should be 400mm lower than the top of the unit.
| >300mm |
|
|
>20mm >20mm | >1000mm | >20mm | >20mm |
| (front side) |
|
|
A vertical view of the outdoor unit |
|
2. Delivery of outdoor unit
As there is no protective package for the outdoor unit, so the following points merit attention:
(1)When forklift is used, insert the fork into the holes in the base plate. (2)When crane is used, lift the unit with 4 pieces of steel rope with diameter
above 6 mm.
(3)Put protective materials between the cable and the unit to prevent deformation and damage of the surface.
Wire rope Protection cushion
| Base panel |
20 | Wire rope |
19