In the case of new ceiling< After installation on the ceiling > Installation Procedure

(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.)

Refer to paper pattern for dimension of ceiling hole.

Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation. Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration.

Contact your real estate dealer

(3) Install a suspending bolt.(Use a M10 bolt)

<Installation example>

Anchor bolt

To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new ceiling, use built-in type bolt or parts prepared in the field.

Before going on installing adjust space between ceiling.

4Installation of indoor unit

In the case of new ceiling

(1) Install unit temporarily

50~150

Roof

Long nut

Suspending bolt

 

Ceiling

Note: All the above mentioned parts shall be prepared in field.

In the case of ceiling already exists Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.

(2)Manual background As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details.

Manual background Center of the hole is marked on the paper pattern.

Center of the unit is marked on the card in the unit and on the paper pattern.

Manual background Mount paper pattern 5 onto unit using 3 screws 6 . Fix the corner of the drain pan at piping outlet.

< After installation on the ceiling >

(3)Adjust unit to its right position. (Refer to preparation for the installation-(1))

(4)Check unit's horizontal level.

Manual background Watert pump and flating switch is installed inside indoor unit, check four corners of the unit for its level using horizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage, problem may occur on floating switch, causing water leakage.)

(5)Remove the washer mounlting 2 , and tighten the nut above.

(6)Remove the paper pattern.

 

Nut (Prepare in field)

In the case of ceiling already exists

Washer (Prepared in field)

 

 

(1) Install unit temporarily

Manual background Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket. Fix the bracket firmly.

(2)Adjust the height and position of the unit. (Refer to preparation for the installation (1) ).

(3)Proceed with (3) and (4) of "In the case of new ceiling".

Suspending bolts

2

 

Fasten (double nuts)

Insert

Washer fixing pad (prepared in feild)

Level

Polythene pipe

[ secure the washer firmly]

 

 

18