Installation Procedure
2. Mounting on high ceiling
Side of ornament panel
Side of indoor unit |
|
3. Install ornament panel on indoor unit. | Swing motor |
|
For indoor unit installation, please refer to Installation Manual.
Check whether indoor unit is horizontal with leveler or polythene pipe filled with water , and check that the dimension of the ceiling opening is correct. Take off the lever gauge before install the ornament panel.
Fasten the screws to make the height difference between the two sides of indoor unit less than 5mm.
First fix it with screws temporally.
Where the swing motor locates in the figure of panle just is the location of liquide pipe.
Connect the wires of |
| |
Connect the wire of signal. | Electric control box | |
Fasten the two temporally fixing screws and other two, and tighten the | ||
| ||
four screws. |
|
If no response of remote controller,check whether the wiring is correct, restart remote controller 10 seconds after shut off power supply.
Tighten screws to redrce the thickness of seals between ornament and indoor unit to
If connecting is not made, error code (A7) appears on remote controller. So, make proper connecting.
Indoor unit | Seal |
| |
Ceiling material |
|
| 5 _ 8mm |
| Ornament panel |
If screws are not tighten tight, problems in Fig.3 might occur.
Tighten screws properly.
Gas leakage.
Gas leakage from roof.
Contamination | Mist exists and drop down. |
If indoor unit is at horizontal level and water drainage is smooth, then, indoor unit height can be adjusted throrgh holes at corners of ornament panel.
Caution
If there are still space after tightening of screws, please readjust the height of indoor unit.
Leave no space.
23