Haier HPU-48CJ03, HPU-42CH03, HPU-42HI03, HPU-48HK03, HPU-42HH03 When problems occur, Power supply

Models: HPU-48CK03 HPU-48CJ03 HPU-48HJ03 HPU-42HH03 HPU-48HK03 HPU-42HI03 HPU-42CH03

1 24
Download 24 pages 47.05 Kb
Page 12
Image 12
Power supply

Manual backgroundManual background When problems occur

Power supply

Manual background The parameter of power cord is over 5G 2.5mm2.

Manual background The parameter of connect cord is 4G 0.75mm2 .

Manual background Air conditioner must use an exclusive line (over 30A)

Manual background When installation air conditioner in a wet place, try to use a circuit breaker against current leakage.

Manual background For installation in other places, use circuit breaker as far as possible.

Manual background The breaker of the air conditioner should be all-pole switch ; and the distance between its two contacts should be no less than 3 mm.

Manual background Such means for disconnection must be incorporation in the fixed wiring

10

Page 12
Image 12
Haier HPU-48CJ03, HPU-42CH03, HPU-42HI03, HPU-48HK03, HPU-42HH03, HPU-48HJ03, HPU-48CK03 When problems occur, Power supply