1.Installation of Outdoor Unit

Install according to Drawing for the installation of indoor and outdoor units

2.Connection of pipes

1.Installation of Outdoor Unit To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radius should be 30 to 40 mm or longer.

2.Connection of pipes Connecting the pipe of gas side first makes working easier. 3.Connection The connection pipe is specialized for R410A.

Half union

 

 

Flare nut

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Forced fastening without careful centering may damage the threads and cause a leakage of gas.

Spanner

Torque wrench

Pipe Diameter

Fastening torque

 

 

Liquid side 6.35mm(1/4")

18N.m

 

 

Gas side 9.52mm(3/8")

42N.m

 

 

Gas side 12.7mm(1/2")

55N.m

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.

The standard pipe length is 5m. If it is over 5m, the function of the unit will be affected. If the pipe has to be lengthened, the refrigerant should be charged, according to 20 g/m. But the charge of refrigerant must be conducted by professional air conditioner engineer. Before adding additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge additional refrigerant.

Outdoor unit

 

 

 

Outdoor unit

 

A

Oil trap

 

 

 

 

 

 

Indoor unit

 

 

 

Max. Length:A=20m

Indoor unit

CAUTION

 

In case more than 5m

Max.Elevation:10m

Oil trap shoud be installed every 5~7m

no more gas if the length of connecting pipe is less than35m

 

3.Connection

 

 

 

Use the same method on indoor unit. Loosen

If wiring is not correct, proper operation can

the screws on terminal block and insert the

 

not be carried out and controller may be

plugs fully into terminal block, then tighten the

damaged.

screws.

 

Fix the cable with a clamp.

4.Attaching Drain-Elbow Insert the cable according to terminal number in the same manner as the indoor unit.

4.Attaching Drain-Elbow

Manual background If the drain-elbow is used, please attach it as figure.

Note: Only for heat pump unit.

Drain hose

Drain elbow Manual backgroundManual backgroundManual backgroundManual backgroundManual background