Haier HSU-09HEK03 Outdoor unit 1.Connection of pipes, Attaching Drain-Elbow, Purging Method

Models: HSU-12LEK13 HSU-12HEK03 HSU-12LEK03 HSU-09HEK03 HSU-07LEK03 HSU-07HEK03 HSU-09LEK03 HSU-09LEK13

1 4
Download 4 pages 48.72 Kb
Page 4
Image 4
Outdoor unit

Outdoor unit

Outdoor unit 1.Connection of pipes

Outdoor unit 1.Connection of pipes To bend a pipe, give the roundness as large as possible not to crush the pipe

2.Attaching Drain-Elbow Connecting the pipe of gas side first makes working easier.

3.Purging Method: The max vertical distance between the indoor unit and the outdoor unit is 5 m.

Half union

Flare nut

Spanner

Torque wrench

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.

Forced fastening without careful centering may damage the threads and cause a leakage of gas.

Pipe Diameter ( )

Fastening torque

 

 

 

Liquid side

6.35mm(1/4")

18N.m

Liquid side

9.52mm(3/8")

40N.m

 

 

Gas side 9.52mm(3/8")

40N.m

Gas side 12.7mm(1/2")

50N.m

Gas side 15.88mm(5/8")

60N.m

2.Attaching Drain-Elbow

for 22k 24k If the drain-elbow is used, please attach it as figure. (Note: Only for heat pump unit.)

3.Purging Method:

Push the air out of the indoor unit and piping as followes:

Manual background Tighten the caps on the valves with specified torque.

 

Tighten torque N.m

 

 

Valve rod

7-9

 

 

Valve cap

20-25

 

 

Manual background When connecting pipe exceeds 5 meters, 20g or 60g(only for 22k 24k) refrigerant shall be added per exceeding meter. Charge according to the following list.

 

for 5k 7k 9k 10k 12k 13k 18k

Piping length

5m

7m

10m

Additional amount

No need

40g

100g

 

 

for 22k 24k

 

Piping length

5m

7m

10m

20m

Additional amount

No need

120g

300g

900g

Indoor unit

A

 

A

 

Outdoor unit

Outdoor unit

B

B

Indoor unit

 

 

Max.Elevation: for 5K 7K 9K 10K 12K 13K: B=5m for 18K 22K 24K: B=10m

Max. Length:

for 5K 7K 9K 10K: A=7m

 

for 12K

13K:

A=10m

 

for 18K

22K 24K:

A=20m

Outdoor unit

A

Oil trap

 

 

C

BIndoor unit

CAUTION

Manual background In case more than 5 metresoil trap C should be installed every 5~7m.

4

Page 4
Image 4
Haier HSU-09HEK03, HSU-09LEK13 Outdoor unit 1.Connection of pipes, Attaching Drain-Elbow, Purging Method, for 22k 24k