Outdoor unit
6.Purging Method:To use vacuum pump
Push the air out of the indoor unit and piping as followes:
(1)Remove the valve cap on
(2)Loosen by 1/2 turn the flare nut of gas pipe, which is conneted to
(3)Loosen
(4)Open
(5)Tighten the caps on the valves with specified torque.
| Tighten torque N.m |
|
|
Valve rod | |
|
|
Valve cap | |
|
|
6.35mm(1/4") | 12.7mm(1/2") |
HSU-12CR03-Y
When connecting pipe exceeds 5 meters, 20g refrigerant shall be added per exceeding meter. Charge according to the following list.
Piping length | 5m | 7m | 10m |
Additional amount | No need | 40g | 100g |
|
|
|
|
Note: When extending piping, air inside piping shall be removed by using external refrigerant gas, charge according to the following list.
Brand new outdoor unit is charged 50g more refrigerant than regulated weight. Only for first installation, this extra 50g can be used to purge air in pipes.
During this procedure, 50g refrigerant will be discharged in piping. (This must be strictly controlled within 90o and 10 sec.)
7