Control Panel Features

1.20 Amp Circuit Breakers. Each cir- cuit breaker protects a 125 V~ outlet against short or overload. These are

“push to reset” type.

2.30 Amp Circuit Breaker. Protects the 30 Amp 125 V~ outlet against short or overload. This is “push to reset” type.

3.Duplex 125 V~ GFCI Receptacles. Use these for 125 V~, 60 Hz, single phase loads up to 20 A (combined per duplex outlet).

4.Single 125 V~ Receptacle. Use this for 125 V~, 60 Hz, single phase de- vices up to 30 A.

5.Single 125/250 V~ Receptacle and circuit breakers. Use a 4-blade grounded connector to operate 125/250 V~, 60 Hz, single phase

loads requiring up to 50 Amps of current up to 12,000 Watts (12kW) of power. Use a connector rated to 250 Volts, 50 Amps with a same-rated

4-wire set. The 50 Amp circuit break- ers protect each hot line of the circuit.

6.Single 12V DC receptacle. Used to power 12VDC loads at 8.3 Amps.

7.Volt / Frequency / Time Digital Me- ter. Used to monitor the AC voltage, frequency and operating speed.

8.Grounding Terminal. Connect to #6 AWG copper wire or larger to connect to an earth-driven copper or brass grounding rod.

9.Amp Circuit Breaker. Protects the 8.3 Amp 12 DC outlet against short or overload. This is “push to reset” type.

10.Voltage Switch. 240V on the left, 120V on the right.