SYMBOLOGY

Table A

RECOMMENDED MINIMUM WIRE GAUGE FOR EXTENSION CORDS*

(120 VOLT)

NAMEPLATE

 

 

 

 

 

AMPERES

 

EXTENSION CORD LENGTH

 

(At Full Load)

 

 

 

 

 

 

 

25

50

75

100

150

 

 

Feet

Feet

Feet

Feet

Feet

0 – 2.0

18

18

18

18

16

2.1

– 3.4

18

18

18

16

14

3.5

– 5.0

18

18

16

14

12

5.1

– 7.0

18

16

14

12

12

7.1 – 12.0

16

14

12

10

-

12.1

– 16.0

14

12

10

-

-

16.1

– 20.0

12

10

-

-

-

* Based on limiting the line voltage drop to five volts at 150% of the rated amperes.